North american hazardous location approval – Rockwell Automation 1747-AENTR SLC to EtherNet/IP Adapter Installation Instructions User Manual
Page 4
 
4 SLC 500 EtherNet/IP Adapter
Publication 1747-IN521B-EN-E - January 2013
North American Hazardous Location Approval
The 1747-AENTR module is North American Hazardous Location approved.
The following information applies when operating 
this equipment in hazardous locations:
Informations sur l’utilisation de cet équipement en 
environnements dangereux:
Products marked "CL I, DIV 2, GP A, B, C, D" are 
suitable for use in Class I Division 2 Groups A, B, C, 
D, Hazardous Locations and nonhazardous locations 
only. Each product is supplied with markings on the 
rating nameplate indicating the hazardous location 
temperature code. When combining products 
within a system, the most adverse temperature 
code (lowest "T" number) may be used to help 
determine the overall temperature code of the 
system. Combinations of equipment in your system 
are subject to investigation by the local Authority 
Having Jurisdiction at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne 
conviennent qu'à une utilisation en environnements de 
Classe I Division 2 Groupes A, B, C, D dangereux et non 
dangereux. Chaque produit est livré avec des 
marquages sur sa plaque d'identification qui indiquent 
le code de température pour les environnements 
dangereux. Lorsque plusieurs produits sont combinés 
dans un système, le code de température le plus 
défavorable (code de température le plus faible) peut 
être utilisé pour déterminer le code de température 
global du système. Les combinaisons d'équipements 
dans le système sont sujettes à inspection par les 
autorités locales qualifiées au moment de l'installation.
EXPLOSION HAZARD
•
Do not disconnect equipment unless 
power has been removed or the area 
is known to be nonhazardous. 
•
Do not disconnect connections to this 
equipment unless power has been 
removed or the area is known to be 
nonhazardous. Secure any external 
connections that mate to this 
equipment by using screws, sliding 
latches, threaded connectors, or other 
means provided with this product.
•
Substitution of any component may 
impair suitability for Class I, 
Division 2.
•
If this product contains batteries, they 
must only be changed in an area 
known to be nonhazardous.
RISQUE D’EXPLOSION
•
Couper le courant ou s'assurer que 
l'environnement est classé non dangereux 
avant de débrancher l'équipement.
•
Couper le courant ou s'assurer que 
l'environnement est classé non dangereux 
avant de débrancher les connecteurs. 
Fixer tous les connecteurs externes reliés 
à cet équipement à l'aide de vis, loquets 
coulissants, connecteurs filetés ou autres 
moyens fournis avec ce produit.
•
La substitution de tout composant peut 
rendre cet équipement inadapté à une 
utilisation en environnement de Classe I, 
Division 2.
•
S'assurer que l'environnement est classé 
non dangereux avant de changer les piles.
WARNING: When you insert or remove the module while backplane power is on, an 
electrical arc can occur. This could cause an explosion in hazardous location 
installations.
Be sure that power is removed or the area is nonhazardous before proceeding. 
Repeated electrical arcing causes excessive wear to contacts on both the module and 
its mating connector. Worn contacts may create electrical resistance that can affect 
module operation.
WARNING: When used in a Class I, Division 2, hazardous location, this equipment 
must be mounted in a suitable enclosure with proper wiring method that complies 
with the governing electrical codes.