Certifications – Rockwell Automation 1794-AENT FLEX I/O EtherNet/IP Adapter Module Installation Instructi User Manual

Page 7

Advertising
background image

FLEX I/O EtherNet/IP Adapters Installation Instructions 7

Publication 1794-IN082C-EN-P - October 2007

Environmental Specifications

Certifications

Mounting Dimensions

Flex I/O, Allen-Bradley, ControlLogix, Rockwell Automation, RSLogix 5000, and RSLinx are trademarks
of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Attribute

Value

Temperature,

operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F)

Temperature,

nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
–40…85 °C (–40…185 °F)

Relative
humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating

Damp Heat):
5…95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz

Shock, operating IEC60068-2-27 (Test Ea, Unpackaged shock):

30 g

Shock,
nonoperating

IEC60068-2-27 (Test Ea, Unpackaged shock):
50 g

Emissions

CISPR 11:
Group 1, Class A

ESD immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF
immunity

IEC 61000-4-3:
10 V/m with 1 kHz sine-wave 80% AM from 80…2000
MHz

10 V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10 V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

3 V/m with 1 kHZ sine-wave 80% AM from
2000…2700MHz

EFT/B immunity

IEC 61000-4-4:
±4 kV at 5 kHz on power ports
±2 kV at 5 kHz on communication ports

Surge transient
immunity

IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power
ports
±2 kV line-earth (CM) on communication ports

Conducted RF
immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150
kHz…80 MHz

Certification

(when product
is marked

(1)

(1)

See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates and
other certification details.

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for
US and Canada (See UL file E65584)

UL Listed for Class I, Division 2, Groups A, B, C and D
Hazardous locations, certified for US and Canada (See
UL file E194810)

CE

European Union 2004/108/EEC EMC Directive,
compliant with:

EN 61326; Meas./Control/Lab., Industrial
Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN61131-2; Programmable Controllers (Clause 8, Zone
A & B)

C-Tick

Australian Radiocommunications Act compliant with

AS/NZS CISPR 11, Industrial Emissions

EtherNet/IP

ODVA conformance tested to EtherNet/IP
specifications

mm
(in.)

A = DIN rail.
B = Secure DIN rail approximately every 200 mm (7.87 in.).

(3.4)

87

(3.7)

94

1794-AENT

(3.4H x 3.7W x 2.7D)

87H x 94W x 69D

30

(1.2)

50

(2.2)

A

B

(3.2)

80

Advertising