Checking LED Indicators

STATUS

The STATUS indicator reports the status of the scanner. The following
table lists the LED states for STATUS:

This state:

Means:

Take this action:

Yellow

The scanner is running POST.

None

Flashing green

The scanner is in idle mode and is
not scanning I/O.

None

Solid green

The scanner is scanning I/O.

None

Flashing red

An I/O fault has occurred.

Check software to identify
fault condition.

Solid red

A scanner internal fault has
occurred.

Power system off and back on. If
the problem persists, service may
be required.

Off

The adapter is not powered up.

Turn on power.

PCI INTERFACE

STATUS

BATT

LED 1

LED 2

LED 3

LED 4