Environment and enclosure, Prevent electrostatic discharge – Rockwell Automation 1769-L23E-QB1B_QBFC1B_QBFC1B CompactLogix Packaged Controller Installation Instructions User Manual

Page 3

Advertising
background image

CompactLogix Controller 3

Rockwell Automation Publication 1769-IN082C-EN-P - February 2013

Environment and Enclosure

Prevent Electrostatic Discharge

WARNING: This equipment is intended for use in a Pollution Degree 2 industrial environment, in
overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to
2000 meters (6562 ft) without derating.

This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR
Publication 11. Without appropriate precautions, there may be potential difficulties ensuring
electromagnetic compatibility in other environments due to conducted as well as radiated
disturbance.

This equipment is supplied as open-type equipment. It must be mounted within an enclosure that
is suitably designed for those specific environmental conditions that will be present and
appropriately designed to prevent personal injury resulting from accessibility to live parts. The
enclosure must have suitable flame-retardant properties to prevent or minimize the spread of
flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The
interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific enclosure type ratings that are
required to comply with certain product safety certifications.

In addition to this publication, see the following:

Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley

® publication

1770-4.1

,

for additional installation requirements

NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of
the degrees of protection provided by different types of enclosure

WARNING: This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle this equipment:

Touch a grounded object to discharge potential static.

Wear an approved grounding wrist-strap.

Do not touch connectors or pins on component boards.

Do not touch circuit components inside the equipment.

Use a static-safe workstation, if available.

Store the equipment in appropriate static-safe packaging when not in use.