Select the packaged controller’s operating mode – Rockwell Automation 1769-L23E-QB1B_QBFC1B_QBFC1B CompactLogix Packaged Controller Installation Instructions User Manual

Page 35

Advertising
background image

CompactLogix Controller 35

Rockwell Automation Publication 1769-IN082C-EN-P - February 2013

The Upgrade Status dialog box indicates that the firmware upgrade has been successfully
completed.

9. Click OK.

10. To close the ControlFLASH utility, click Cancel and then click Yes.

Select the Packaged Controller’s Operating Mode

Use the keyswitch on the front panel of the packaged controller to select the packaged
controller’s operating mode.

Use this
operating mode

To achieve these tasks

RUN

Upload projects.
Run the program and enable outputs.
When the keyswitch is in the RUN position, you cannot change the operating mode by using the Controller
Status menu in RSLogix 5000 software.

PROG

Disable outputs.
Upload/download projects.
Create, modify, and delete tasks, programs, or routines.
Stop the execution (scanning) of tasks. That is, the packaged controller does not execute (or scan) tasks

while the keyswitch is in the Prog position.

When the keyswitch is in the PROG position, you cannot change the operating mode by using the
Controller Status menu in RSLogix 5000 software.

REM

Upload/download projects.
Switch between Remote Program, Remote Test, and Remote Run modes by using the Controller Status

menu in RSLogix 5000 programming software.

These Remote modes are can be selected using the Controller Status menu:

Remote Run - In this mode, the controller executes (scans) tasks, enables outputs, and enables
online edits.
Remote Program - In this mode, the controller: disables outputs, allows program and task edits
while online, downloads projects, and inhibits execution (scanning) of tasks.
Remote Test - In this mode, the controller executes tasks with outputs disabled and enables online
editing.