Specifications – Rockwell Automation 1757-FIM ProcessLogix Fieldbus Interface Module (FIM) Installation Instructions User Manual

Page 8

Advertising
background image

8 ProcessLogix Fieldbus Interface Module (FIM)

Publication 1757-IN913A-EN-P - October 2001

Specifications

FIM Specifications

Physical Interface

H1 FOUNDATION Fieldbus

Number of H1 Networks per FIM

1

(Each network defined as

a F

OUNDATION

Fieldbus 31.25 kbps H1 network)

2

Maximum Number of Fieldbus Devices per H1 Network

30

2

Maximum Number of FIMs per 1757-PLX52 Controller
(Each FIM counts as 3 IOMs in the IOMs/CPM
calculation.)

21

Maximum Number of Fieldbus Devices per 1757-PLX52
Controller

1260

2

Maximum Number of FIMs per Server (Redundant or
Non-Redundant)

100

Maximum Number of H1 Networks per Server (Redundant
or Non-Redundant)

200

Maximum Number of Fieldbus Devices per Server

3000

Maximum Single-Variable Publications per Second on an
H1 network

15

Maximum number of VCRs (Virtual Communications
Relationships) per Network

64

3

Electro-static Discharge

IEC 1000-4-2: 1995

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock):
0 to 60°C (32 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged
Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged
Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged
Non-operating Thermal Shock):
–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged
Non-operating
Damp Heat):
5 to 95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
0.5g @ 10-500Hz

Shock

IEC 60068-2-27: Test Ea (Unpackaged shock,
ES#002)
Operating 5g
Non-operating 20g

Advertising