Install the armorpoint ac output module – Rockwell Automation 1738-OA2M12AC3 ArmorPoint AC Output Module, Series A User Manual
Page 5
Advertising
Publication 1738-IN007A-EN-E - June 2004
ArmorPoint AC Output Module, Series A 5
3. Mount the base using #8 (M4) screws.
4. Ground the system using the ground lug connection. (The
ground lug connection is also a mounting hole.)
Install the ArmorPoint AC
Output Module
To install the ArmorPoint AC output module, proceed as follows.
1. Using a bladed screwdriver, rotate the keyswitch on the
mounting base clockwise until the number 8 aligns with the
notch in the base.
2. Position the module vertically above the mounting base. The
module will bridge two bases.
Ground lug connection
Latching mechanism
Keyswitch-
Set to position 8 for
the 1738 AC output
module
Mounting base
43675
1738-OA2M12AC3/A
12V ac
0.75Amp
Out
0
1
0
1
M
N
O
D
E
T
Module will bridge two bases.
43778
Advertising