ArmorPoint AC Output Module, Series A 7

Wire the AC Output Module

Following are wiring instructions for the ArmorPoint AC output
module.

1738-OA2M12AC3

Communicate With

Your Module

I/O messages are sent to (consumed) and received from (produced)
the ArmorPoint I/O module. These messages are mapped into the
processor’s memory. This ArmorPoint I/O output module consumes 1
byte of output data (scanner Tx - status). It does not produce data
(scanner Rx).

Default Data Map for the ArmorPoint AC Output Modules

1738-OA2M12AC3

Message size: 1 Byte

ATTENTION

Make sure all connectors and caps are securely
tightened to properly seal the connections against
leaks and maintain IP67 requirements.

(view into connector)

Pin 1 - Chassis

Pin 2 - L2/N

Pin 3 - Output 0 (M12-A)

Output 1 (M12-B)

43761

7

6

5

4

3

2

1

0

Produces
(scanner Rx)

Not Used

Channel status

Consumes
(scanner Tx)

Not Used

Ch1

Ch0

Output state

Where: 0 = off, 1 = on