Default data map for the module – Rockwell Automation 1738-IE4CM12 ArmorPoint 4-Channel 24V dc Analog Input Modules, Series A User Manual
Page 9

ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 9
Publication
1738-IN024C-EN-P - March 2010
Default Data Map for the Module
1738-IE4CM12
Message size: 12 Bytes
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Produces
(Scanner Rx)
Input Channel 0 High Byte
Input Channel 0 Low Byte
Input Channel 1 High Byte
Input Channel 1 Low Byte
Input Channel 2 High Byte
Input Channel 2 Low Byte
Input Channel 3 High Byte
Input Channel 3 Low Byte
Status Byte for Channel 1
Status Byte for Channel 0
O
R
U
R
H
H
A
L
L
A
H
A
L
A
C
M
C
F
O
R
U
R
H
H
A
L
L
A
H
A
L
A
C
M
C
F
Status Byte for Channel 3
Status Byte for Channel 2
O
R
U
R
H
H
A
L
L
A
H
A
L
A
C
M
C
F
O
R
U
R
H
H
A
L
L
A
H
A
L
A
C
M
C
F
Consumes
(scanner Tx)
No consumed data
Where:
CF = Channel Fault Status, 0 = no error, 1 = fault
CM = Calibration Mode; 0 = normal, 1 = calibration mode
LA = Low Alarm; 0 = no error, 1 = fault
HA = High Alarm; 0 = no error, 1 = fault
LLA = Low/Low Alarm; 0 = no error, 1 = fault
HHA = High/High Alarm; 0 = no error, 1 = fault
UR = Underrange; 0 = no error; 1 = fault
OR = Overrange; 0 = no error; 1 = fault