Terminal block removal, Switch settings to select voltage or current input – Rockwell Automation 1746-NI8 SLC 500 Analog Input Module Instructions User Manual
Page 8
Advertising
![background image](/manuals/579802/8/background.png)
8 SLC 500™ Analog Input Module
Publication 1746-IN006A-US-P
Terminal Block Removal
To remove the terminal block:
1. Loosen the two terminal block release screws.
.
2. Grasp the terminal block at the top and bottom and pull outward and down.
Switch Settings to Select Voltage or Current Input
Before installing the module in the chassis, use the DIP switches on the module
circuit board to select between voltage and current inputs for channels 0 through 7.
The switch settings are
• OFF = VOLTAGE INPUT
• ON = CURRENT INPUT.
Terminal Block Release
Screws
Maximum Torque =
0.7 to 0.9 Nm (6 to 8 in-lbs)
O
2
1
N
O
2
1
N
O
2
1
N
O
2
1
N
VOLTAGE
CURRENT
CH7
CH0
@JO"VTQQE
@JO"VTQQE
".
".
Advertising