8 SLC 500™ Analog Input Module

Publication 1746-IN006A-US-P

Terminal Block Removal

To remove the terminal block:

1. Loosen the two terminal block release screws.

.

2. Grasp the terminal block at the top and bottom and pull outward and down.

Switch Settings to Select Voltage or Current Input

Before installing the module in the chassis, use the DIP switches on the module
circuit board to select between voltage and current inputs for channels 0 through 7.
The switch settings are

• OFF = VOLTAGE INPUT

• ON = CURRENT INPUT.

Terminal Block Release
Screws

Maximum Torque =
0.7 to 0.9 Nm (6 to 8 in-lbs)