Status indicator, Specifications, Output map – Rockwell Automation 1794-OF4I FLEX I/O Isolated Analog Output Module Installation User Manual

Page 4: Configure the output channels, General specifications, Environmental specifications

Advertising
background image

4 FLEX™ I/O Isolated Output Analog Module

Publication 1794-IN037E-EN-P - November 2011

Status Indicator

The OK status indicator is two-colored: red and green. The indicator flashes green
for one of three reasons:

1. The module configuration word is zero (for example, power up reset

condition).

2. The 24V DC user power is off.
3. The module is in configuration mode.

The indicator displays red to indicate that the module did not pass the initial
hardware test. Cycle power again.
After power up, if the status indicator is not flashing green or solid green, cycle
module power once more to verify a proper reset of the bus interface.

Specifications

Output Map

Dec

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Word 0

EN

S1

S0

0

0

0

0

0

0

0

0

0

0

0

0

0

Word 1

Output data channel 0

Word 2

Output data channel 1

Word 3

Output data channel 2

Word 4

Output data channel 3

Word 5

Ch 3 configuration

Ch 2 configuration

Ch 1 configuration

Ch 0 configuration

Word 6

IC

1

TR

IT

Q3

Q2

Q1

Q0

RV

QK

CK

GO

Channel number

Where:

EN = Inable output; 0 = Output follows S1/S0, 1 = Output enabled

S1/S0 = Safe state source

IC = Initiate configuration bit

TR = Transparent bit

IT = Interrupt toggle bit

Q0…Q3 = Requests for outputs to hold

RV = Revert to default bit

QK = Quick calibration

CK = Calibration clock

GO = Gain offset select

Configure the Output Channels

Configuration Bits

Nominal Range

Data Type

Output Values

Module Update
Rate

MSD

LSD

0

0

0

1

4...20 mA

Signed 2’s
complement

<0000…7878>

5.0 ms

0

0

1

0

±10V

<831F…7CE1>

2.5 ms

0

0

1

1

±5V

<8618…79E8>

2.5 ms

0

1

0

0

0...20 mA

Signed 2’s
complement %

0…10000>

5.0 ms

0

1

0

1

4…20 mA

<0…10000>

5.0 ms

0

1

1

0

0…10V

0…10000

5.0 ms

0

1

1

1

±10V

<-10000…10000>

5.0 ms

1

0

0

0

0…20 mA

Binary

0000…F3CF

2.5 ms

1

0

0

1

4…20 mA

0000…F0F1

5.0 ms

1

0

1

0

0…10V

0000…F9C2

2.5 ms

1

0

1

1

0…5V

0000…F3CF

2.5 ms

1

1

0

0

0…20 mA

Offset binary

<0618…F9E8>

2.5 ms

1

1

0

1

4…20 mA

<8000…F878>

5.0 ms

1

1

1

0

±10V

<031F…FCE1>

2.5 ms

1

1

1

1

±5V

<0618…F9E8>

2.5 ms

General Specifications

Attribute

Value

Number of outputs

4 isolated

Module location

1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, 1794-TB3TS, 1794-TBN

FlexBus voltage

5V DC

FlexBus current

50 mA

External DC power supply,
nom voltage range

24V DC

19.2…31.2V DC (includes 5% AC ripple)

External DC power supply
current

210 mA @ 24V DC

Thermal dissipation, max

16 BTU/hr @ 31.2V DC

Power dissipation, max

4.7 W @ 31.2V DC

Isolation voltage

120V (continuous), Basic Insulation Type, channel to channel, channel to user,
channel to system, and user power to system when used with 1794-TB2,
1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS.

250V (continuous), Basic Insulation Type, channel to channel, channel to user,
channel to system, and user power to system when used with 1794-TBN.

Type tested at 1000V AC for 60 s.

Data format

2’s complement

2’s complement %

Binary

Offset binary

Indicators

1 red/green power/status indicator

Keyswitch position

4

Dimensions, with module
installed in base; HxWxD

94.0 x 94.0 x 66.0 mm

(3.7 x 3.7 x 2.6 in.)

Conductor category

(1)

2 – on signal ports

2 – on power ports

Conductor wire size

Determined by installed terminal base

Wire type

Shielded on signal ports

North American temp code

T4A

IEC temp code

T4

(1)

Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

Module Specifications – 1794-OF4I

Attribute

Value

Resolution

Voltage

Current

15 bits plus sign

0.320 mV/cnt

0.656 mA/cnt

Conversion type

Digital-to-analog converter

Update rate

2.5/5.0 ms all channels (see

Configure the Output Channels

table)

Output current terminal

0 mA output until module is configured

4…20 mA (user configurable)

0…20 mA (user configurable)

Output voltage terminal

0V output until module is configured

±10V (user configurable)

0…10V (user configurable)

±5V (user configurable)

0…5V (user configurable)

Step response to 63% of full
scale

< 25

s

Current load on voltage
output, max

3 mA

Resistive load on voltage
output

0…750

Absolute accuracy

Voltage terminal

Current terminal


0.1% full scale @ 25 °C

0.1% full scale @ 25 °C

Accuracy drift w/temperature

Voltage terminal

Current terminal


0.0012% full scale/°C

0.0025% full scale/°C

Calibration

Factory calibrated; can be recalibrated when necessary.

Maximum overload

30V continuous or 32 mA continuous, one channel at a time.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…55 °C (-4…131 °F)

Temperature, surrounding air,
max.

55 °C (131 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged shock):

30 g

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged shock):

50 g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

General Specifications