Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±2 kV @ 5 kHz on power ports

±2 kV @ 5 kHz on shielded signal ports

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports

±2 kV line-earth(CM) on shielded signal ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Enclosure type rating

None (open-style)

Certifications (when product is marked)

(1)

Attribute

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL

File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified

for U.S. and Canada. See UL File E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D

Hazardous Locations. See CSA File LR69960C.

Ex

European Union 94/9/EC ATEX Directive, compliant with:

EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements

II 3 G Ex nA IIC T4 X

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers (Clause 11

C-Tick

Australian Radiocommunications Act compliant with:

AS/NZS CISPR 11, Industrial Emissions

TÜV

TÜV Certified for Functional Safety

(2)

:

Capable of SIL 2

(1)

For the latest up-to-date information, see the Product Certification link at

www.ab.com

for Declarations of

Conformity, Certificates and other certification details.