MicroLogix 1762-OW16 Relay Output Module 13

Publication 1762-IN009C-EN-P - July 2013

Wiring the Finger-Safe Terminal Block

When wiring the terminal block, keep the finger-safe cover in place.

1. Route the wire under the terminal pressure plate. You can use the stripped end of the

wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.

2. Tighten the terminal screw making sure the pressure plate secures the wire.

Recommended torque when tightening terminal screws is 0.90 Nm (8 lb-in.).

Wire Size and Terminal Screw Torque

Each terminal accepts up to two wires with the following restrictions:

TIP

Finger-safe cover not shown for clarity.

TIP

If you need to remove the finger-safe cover, insert a screw driver into one of the
square wiring holes and gently pry the cover off. If you wire the terminal block
with the finger-safe cover removed, you will not be able to put it back on the
terminal block because the wires will be in the way.

Wire Type

Wire Size

Terminal Screw Torque

Solid

Cu-90 °C (194 °F)

#14 …22 AWG

0.90 Nm (8 lb-in.)

Stranded

Cu-90 °C (194 °F)

#16…22 AWG

0.90 Nm (8 lb-in.)