5a (also see – Rockwell Automation 1762-OW16 Relay Output Module User Manual

Page 16

Advertising
background image

16 MicroLogix 1762-OW16 Relay Output Module

Publication 1762-IN009C-EN-P - July 2013

Isolated groups

Group 1: Outputs 0…7
Group 2: Outputs 8…15

Output group to backplane isolation

Verified by one of the following dielectric tests: 1836V AC for 1 sec.
or 2596V DC for 1 sec.

265V AC working voltage (IEC Class 2 reinforced insulation)

Output group to output group isolation

Verified by one of the following dielectric tests: 1836V AC for 1 sec.
or 2596V DC for 1 sec.

265V AC working voltage (basic insulation)
150V AC working voltage (IEC Class 2 reinforced insulation)

Vendor ID code

1

Product type code

7

Product code

121

Relay Contact Ratings

Volts (max.)

Continuous
Amps per Point
(max.)

Amperes

(1)

(1)

Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication

1770-4.1

.

Voltamperes

Make

Break

Make

Break

240V AC

2.5A

7.5A

0.75A

1800 VA

180 VA

120V AC

15A

1.5A

125V DC

1.0A

0.22A

(2)

(2)

For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 14V, the make/break rating
for relay contacts cannot exceed 2A.

28 VA

24V DC

2.0A

1.2A

28 VA

Output Specifications

Attribute

Value

Advertising