Configuring your input module, Configuring your output module, Specifications – Rockwell Automation 1794-IV16_OV16_OV16P Flex I/O Digital DC Sourcing Input and Sinking Output Modules I.I. User Manual

Page 3

Advertising
background image

3

Publication 1794-IN095A-EN-P - April 2004

Wiring Connections for the 1794-IV16, 1794-OV16 and
1794-OV16P

1794-TB2, -TB3 and -TB3S Terminal Base Wiring for 1794-IV16,
1794-OV16 and 1794-OV16P

2 and 3-Wire Input Wiring for 1794-IV16

Configuring Your Input Module

You configure your input module by setting bits in the configuration
word (word 3).

Setting the Input Filter Time for the 1794-IV16

To set the input filter time, set the associated bits in the output image
(complementary word) for the module.

For example, to set a filter time of 8ms for a dc input module at address rack 1,
module group 0, in configuration word 3, set bits 08, 09 and 10 as shown
below.

Refer to the table for additional filter times available.

Input Filter Times

Configuring Your Output Module

You configure your output module by setting bits in word 1.

Specifications

Channel

Signal

Power Terminal

Common Terminal

1

1794-OV16, 1794-OV16P,
1794-IV16

1

1794-IV16

0

A-0

C-35

B-17

1

A-1

C-36

B-18

2

A-2

C-37

B-19

3

A-3

C-38

B-20

4

A-4

C-39

B-21

5

A-5

C-40

B-22

6

A-6

C-41

B-23

7

A-7

C-42

B-24

8

A-8

C-43

B-25

9

A-9

C-44

B-26

10

A-10

C-45

B-27

11

A-11

C-46

B-28

12

A-12

C-47

B-29

13

A-13

C-48

B-30

14

A-14

C-49

B-31

15

A-15

C-50

B-32

+V dc

C-34 thru C-51 are internally connected together

Common

B-16 thru B-33 are internally connected together

1

2-wire sourcing input devices use the input and common terminals.

3-wire sourcing input devices use the input, common and power terminals.

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read 0

I15

I14

I13

I12

I11

I10

I9

I8

I7

I6

I5

I4

I3

I2

I1

I0

Read 1

C = Counter Input value of input 15

Write

Not used

CR

CF

NU

Input Filter FT 0-15

Not used

WhereI = Input

C = Counter value for input 15

FT = Input filter tim

CR = Counter Reset

CF = Counter Fast - where 1 = Fast input (raw) data; 0 = Standard input filtered data

NU = Not used

Note: C, CR and CF not available when used with any series 1794-ASB or -ASB2 Remote I/O Adapters.

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

Inputs/Outputs

Commons

(1794-TB3 shown)

Connect V dc common to terminal B-16
Connect +V dc power to terminal C-34

-V

Voltage
In +V

Voltage
Out +V

Voltage

A

B

C

(Use B-33 and C-51 for daisy-chaining to next terminal base unit)

Common

-V

Common

= 24V dc

= Common

= Source Input

0 -15

34-51

16-33

A
B
C

p

/

2-Wire Device

(Sinking Output)

A

B

C

0

1

0

1

3-Wire Device

(Sinking Output)

0

16

34

Bits

Description

Selected

Filter Time

10

09

08

Filter Time for inputs 00-15 (00-17)

0

0

0

Filter Time 0 (Default)

0.25ms

0

0

1

Filter Time 1

0.50ms

0

1

0

Filter Time 2

1ms

0

1

1

Filter Time 3

2ms

1

0

0

Filter Time 4

4ms

1

0

1

Filter Time 5

8ms

1

1

0

Filter Time 6

16ms

1

1

1

Filter Time 7

32ms

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read 0

Not used

Write 1

IO
15

O
14

O
13

O
12

O
11

O
10

O
9

O
8

O
7

O
6

O
5

O
4

O
3

O
2

O
1

O
0

Where

O = Output

Specifications - 16 Source Input Module, Cat. No. 1794-IV16

Number of Inputs

16, nonisolated, sourcing

Module Location

Cat. No. 1794-TB3, -TB3S

On-state Voltage

10V dc minimum
24V dc nominal
31.2V dc maximum

On-state Current

2.0mA minimum
8.0mA nominal at 24V dc
11.0mA maximum

Off-state Voltage

5.0V dc maximum

Off-state Current

1.5mA minimum

Input Impedance

4.7K ohms maximum

Isolation Voltage

Tested at 2121V dc for 1s between user and system
No isolation between individual channels

Flexbus Current

30mA

Power Dissipation

5.7W maximum @ 31.2V dc

Thermal Dissipation

Maximum 19.4 BTU/hr @ 31.2V dc

O:010

09 08 07 06 05 04 03 02 01 00

15 14 13 12 11 10

Dec.

FT = 00 thru 15

0

Fill File
Source
Destination
Length

1280

#O:010

1

FLL

Write FT to complement

of input module.

O:010

00

I:000

Write Filter Time on system startup.

= 2400 Octal or

1280 Decimal

09 08 07 06 05 04 03 02 01 00

15 14 13 12 11 10

Dec.

1

FT for channels 00 thru 15

1

Advertising