Derating Chart for the 1794-IV16

Indicators (field side
indication, customer device
driven)

16 yellow status indicators

Input Filter Time

1

Off to On

On to Off

0.25ms, 0.5ms, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
0.25ms, 0.5ms, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
0.25ms default - Selectable using configuration word 3

1

Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off filter

time is time from the input signal dorpping below the valid level to recoginition by the module.

Specifications - 16 Output Modules 1794-OV16 and -OV16P

1794-OV16

1794-OV16P

Number of Outputs

16, nonisolated, sinking

Module Location

Cat. No. 1794-TB3, -TB3S

On-state Voltage
Range

10V dc minimum
24V dc nominal
31.2V dc maximum

Output Current Rating

8.0A (16 outputs @ 0.5A)

Off-state Voltage

31.2 dc maximum

On-state Current

1.0mA minimum per channel
500mA maximum per channel

Surge Current

2A for 50ms, repeatable every 2s

Off-state Leakage

0.5mA maximum

On-state Voltage Drop

0.2V dc maximum

Isolation Voltage

Tested at 2121V dc for 1s between user and system
No isolation between individual channels

Output Signal Delay

1

Off to On - 0.5ms maximum
On to Off - 1.0ms maximum

Flexbus Current

80mA

Power Dissipation

4.2W maximum @ 31.2V dc

Thermal Dissipation

Maximum 14.3 BTU/hr @ 31.2V dc

Indicators (field side
indication, logic driven)

16 yellow status indicators

Fusing

Module outputs are not fused.
Fusing is recommended. If fusing
is desired, you must provide
external fusing. Use SAN-O
MQ4-800 800mA fuses

Outputs are electronically
protected.

1

The time from the receipt of an on or off command to the output actually turning on or off.

General Specifications

Terminal Base Screw
Torque

7 pound-inches (0.8Nm)

Dimensions (with module
installed)

3.7H x 3.7W x 2.7D inches
94H x 94W x 69D mm

External dc power
Supply voltage
Voltage range

Supply current

24V dc nominal
1794-OV16, -OV16P - 10.0 to 31.2V dc (includes 5% ac ripple)
1794-IV16 - 10 to 31.2V dc (includes 5% ac ripple) (see derating curve)
1794-OV16, -OV16P - 49mA @ 24V dc (21-65mA)

Keyswitch Position

2

Environmental Conditions

Operating
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55°C (32 to 131°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):
5 to 95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
4kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

±1kV line-earth(CM) on shielded ports

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on signal ports

Surge Transient
Immunity

IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Conducted RF
Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Enclosure Type Rating

None (open-style)

Conductors

Wire Size

Category

1

12AWG (4mm

2

) stranded copper wire rated at 75°C or higher

3/64 inch (1.2mm) insulation maximum
2

Certifications (when
product is marked)

2

UL

UL Listed Industrial Control Equipment

CSA CSA Certified Process Control Equipment

CSA CSA certified for Class I, Division 2, Groups A, B, C and

Hazardous locations

EEx

2

European Union 94/9/EEC ATEX Directive, compliant with:

EN 50021; Potentially Explosive Atmospheres,

Protection “n” (Zone 2)

CE

2

European Union 89/336/EEC EMC Directive,

compliant with:

EN 61000-6-4; Industrial Emissions

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

C-Tick

2

Australian Radiocommunications Act compliant with

AS/NZS CISPR 11, Industrial Emissions

1

You use this category information for planning conductor routing as described in Allen-Bradley

publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.

2

For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of
Conformity, Certificates and other certification details. For notification of any additional release notes, refer to

www.ab.com/manuals/.

Voltage

Temperature (max.)

Normal Other

Voltage

Temperature (max.)

Normal Other

31.2

37

32

29.0

51

45

30.5

41

36

28.5

55

48

30.0

45

39

28.0

51

29.5

48

42

27.5

55

0

15

10

25

20

30

31.2

10

20

30

40

50

55

60

V

in

On-state

Voltage

(V dc)

Ambient Temperature

o

C

The area within the curve represents the safe operating range for the module under
various conditions of user supplied 24V dc supply voltages and ambient temperatures.

= Normal mounting safe operating range, (includes ).

= Other mounting positions (including inverted horizontal) safe operating range

37

32

28.5
27.5