Rockwell Automation 1769-OB16 Compact Solid State 24V dc Source Output Module User Manual

Page 10

Advertising
background image

10 Compact™ Solid State 24V dc Source Output Module

Publication 1769-IN054A-EN-P - April 2001

2. Route the wire under the terminal pressure plate. You can use the bare wire

or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.

3. Tighten the terminal screw making sure the pressure plate secures the wire.

Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lbs).

Simplified Output Circuit Diagram

Wire Size and Terminal Screw Torque

Each terminal accepts up to two wires with the following restrictions:

TIP

The terminal screws are non-captive. Therefore, it is
possible to use a ring lug [maximum 1/4 inch o.d. with
a 0.139 inch minimum i.d. (M3.5)} with the module.

TIP

If you need to remove the finger-safe cover, insert a
screw driver into one of the square, wiring holes and
gently pry the cover off. If you wire the terminal block
with the finger-safe cover removed, you will not be
able to put it back on the terminal block because the
wires will be in the way.

Wire Type

Wire Size

Terminal Screw
Torque

Retaining Screw
Torque

Solid

Cu-90°C (194°F)

#14 to #22 AWG

0.68 Nm (6 in-lbs)

0.46 Nm (4.1 in-lbs)

Stranded

Cu-90°C (194°F)

#16 to #22 AWG

0.68 Nm (6 in-lbs)

0.46 Nm (4.1 in-lbs)

Vcc

+VDC

OUT

DC COM

0.1

µ

F

100pF

20K

15K

10K

G

S

D

Advertising