I/o memory mapping, Output data file, Output module’s input data file – Rockwell Automation 1769-OB16 Compact Solid State 24V dc Source Output Module User Manual

Page 11

Advertising
background image

Compact™ Solid State 24V dc Source Output Module 11

Publication 1769-IN054A-EN-P - April 2001

I/O Memory Mapping

Output Data File

For each module, slot x, word 0 in the output data file contains the control
program’s directed state of the discrete output points.

w = write

Output Module’s Input Data File

For each module, slot x, input data file word 0 contains the state of the module’s
output data (output data echo) file word 0. During normal operation, these input
bits represent the logic state that the outputs are directed to by the control program.
They are also dependent upon the:

Program Mode configuration (if supported by the controller)

The Fault Mode configuration (if supported by the controller)

r = read

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

w

w

w

w

w

w

w

w

w

w

w

w

w

w

w

w

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r

IMPORTANT

The output module’s input data file reflects the output data echo
of the module, not necessarily the electrical state of the output
terminals. It does not reflect shorted or open outputs.

It is important to use this input word if the controller adapter
supports the Program Mode or Fault Mode function, and if it is
configured to use them.

Advertising