Remote I/O Adapter Module 13

Publication 1747-IN014C-EN-P - January 2003

Link Termination

A 6-pin keyed connector provides a quick connection to the RIO link and processor
restart lockout switch. A user-supplied terminating resistor must be attached across
lines one and two of the connector at each end of the RIO link. The size of the
resistor depends on the baud rate and whether the scanner and all adapters have
extended node capability, as shown in the table below. The cable shield must be
connected to chassis ground only at one end of the RIO link.

Baud Rate

Resistor size

Using Extended Node

Capability

All Baud Rates

82

1/2 Watt

Not Using Extended

Node Capability

57.6K baud

150

1/2 Watt

115.2K baud

150

1/2 Watt

230.4K baud

82

1/2 Watt

IMPORTANT

If the signal integrity on the RIO link is compromised by
environmental noise, improper termination, and/or improper
cable installation, the 1747-ASB module scan rate drops. This is
indicated by a pronounced flickering of the status display.

IMPORTANT

Do not connect anything to the NC (No Connect) terminal.

To Scanner’s
Connector

Chassis Ground

Terminating Resistor

Terminating Resistor

Blue
Shield
Clear

Line 1 (Blue Wire)
SHLD (Shield wire)
LINE 2 (Clear wire)
NC (No Connect)
IN
RET