Rockwell Automation 1734-IE4C POINT I/O 4 Channel High Density Current Input Module Installat User Manual

Page 13

Advertising
background image

POINT I/O 4 Channel High Density Current Input Module 13

Publication

1734-IN032C-EN-P - June 2012

Default Data Map for the 1734-IE4C Analog Input Module

Message size: 12 Bytes

Byte

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Produces
(scanner
Rx)

Input Channel 0 High Byte

Input Channel 0 Low Byte

Input Channel 1 High Byte

Input Channel 1 Low Byte

Input Channel 2 High Byte

Input Channel 2 Low Byte

Input Channel 3 High Byte

Input Channel 3 Low Byte

Status Byte for Channel 1

Status Byte for Channel 0

O
R

U
R

H
H
A

L
L
A

H
A

L
A

C
M

C
F

O
R

U
R

H
H
A

L
L
A

H
A

L
A

C
M

C
F

Status Byte for Channel 3

Status Byte for Channel 2

O
R

U
R

H
H
A

L
L
A

H
A

L
A

C
M

C
F

O
R

U
R

H
H
A

L
L
A

H
A

L
A

C
M

C
F

Consumes
(scanner
Tx)

No consumed data

Where:

CF = Channel Fault status; 0 = no error, 1 = fault
CM = Calibration Mode; 0 = normal, 1 = calibration mode
LA = Low Alarm; 0 = no error, 1 = fault
HA = High Alarm; 0 = no error, 1 = fault
LLA = Low/Low Alarm: 0 = no error, 1 = fault
HHA = High/High Alarm; 0 = no error, 1 = fault
UR = Underrange; 0 = no error, 1 = fault
OR = Overrange; 0 = no error, 1 = fault