Rockwell Automation 1734-IE4C POINT I/O 4 Channel High Density Current Input Module Installat User Manual
Page 13

POINT I/O 4 Channel High Density Current Input Module 13
Publication
1734-IN032C-EN-P - June 2012
Default Data Map for the 1734-IE4C Analog Input Module
Message size: 12 Bytes
Byte
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Produces
(scanner
Rx)
Input Channel 0 High Byte
Input Channel 0 Low Byte
Input Channel 1 High Byte
Input Channel 1 Low Byte
Input Channel 2 High Byte
Input Channel 2 Low Byte
Input Channel 3 High Byte
Input Channel 3 Low Byte
Status Byte for Channel 1
Status Byte for Channel 0
O
R
U
R
H
H
A
L
L
A
H
A
L
A
C
M
C
F
O
R
U
R
H
H
A
L
L
A
H
A
L
A
C
M
C
F
Status Byte for Channel 3
Status Byte for Channel 2
O
R
U
R
H
H
A
L
L
A
H
A
L
A
C
M
C
F
O
R
U
R
H
H
A
L
L
A
H
A
L
A
C
M
C
F
Consumes
(scanner
Tx)
No consumed data
Where:
CF = Channel Fault status; 0 = no error, 1 = fault
CM = Calibration Mode; 0 = normal, 1 = calibration mode
LA = Low Alarm; 0 = no error, 1 = fault
HA = High Alarm; 0 = no error, 1 = fault
LLA = Low/Low Alarm: 0 = no error, 1 = fault
HHA = High/High Alarm; 0 = no error, 1 = fault
UR = Underrange; 0 = no error, 1 = fault
OR = Overrange; 0 = no error, 1 = fault