18 POINT I/O 4 Channel High Density Current Input Module

Publication

1734-IN032C-EN-P - June 2012

Input
impedance/resistance
conversion type

60

Ω

Sigma Delta

Common mode
rejection ratio

120 dB

Normal mode
rejection ratio

-60 dB
Notch Filter
15.7 Hz @ Notch = 60 Hz (default)
13.1 Hz @ Notch = 50 Hz
26.2 Hz @ Notch = 100 Hz
31.4 Hz @ Notch = 120 Hz
52.4 Hz @ Notch = 200 Hz
62.9 Hz @ Notch = 240 Hz
78.6 Hz @ Notch = 300 Hz
104.8 Hz @ Notch = 400 Hz
125.7 Hz @ Notch = 480 Hz

Data format

Signed integer

Maximum overload

Fault protected to 28.8V DC

Calibration

Factory calibrated

Indicators

1 green/red network status indicator, logic side
1 green/red module status indicator, logic side
4 green/red input status indicators, logic side

(1)

Includes offset, gain, non-linearity and repeatability error terms

IMPORTANT

Refer to Publication

1734-SG001

for information on breaking the field power

distribution bus. See sections “When to Use the Field Power Distributor”
and “When to Use the Expansion Power Unit”.