Chapter 1 Communicating with an ASCII device

To configure the user protocol, use these steps.

1. In the Controller Properties dialog box, click the User Protocol tab.

Enter a buffer size greater than or equal to the greatest number of

characters in a transmission. Twice the number of characters is a good

guideline.

For ABL or ARL instructions, enter termination characters to mark the

end of the data. For ASCII codes, see

ASCII Character Codes

on

page

29

.

If the device sends

Then

Tips

One termination character

In the Termination Character 1 box, type the

hexadecimal ASCII code for the first character.

In the Termination Character 2 box, type $FF.

For printable characters, such as 1 or A, type the character.

Two termination characters

In the Termination Character 1 and 2 boxes, type the

hexadecimal ASCII code for each character.

For AWA instruction, enter append characters. For ASCII codes, see

ASCII Character Codes

on

page 29

.

To append

Then

Tips

One character

In the Append Character 1 box, type the

hexadecimal ASCII code for the first character.

In the Append Character 2 box, type $FF.

For printable characters, such as 1 or A, type the character.

Two characters

In the Append Character 1 and 2 boxes, type the
hexadecimal ASCII code for each character.

Configure the User Protocol

12

Rockwell Automation Publication 1756-PM013D-EN-P - October 2014