14 SynchLink Base Block

Publication 1751-IN001A-EN-P - March 2001

Specifications

Power Supply

To comply with CE Low Voltage directives, you must use a
Safety Extra Low Voltage (SELV) or a Protected Extra Low
Voltage (PELV) power supply to power this base block.

Use a NEC/CEC Class 2 power supply in order to comply with
UL and CSA requirements.

Input Voltage Rating

0.6A @ 24V dc nominal

Output Voltage Rating

1.2A @ 5.1V dc nominal

Input Voltage Range

20V dc to 30V dc
A regulated power supply is recommended.

Communication Rate

5M bit/s

Power Consumption

600mA maximum for external 24V supply based on worst case
block loading (four splitters)

Terminal Block Torque Requirements

5-7 in-lb. maximum

Environmental Conditions

(1)

Operating Temperature

0ºC - 60ºC

Storage Temperature

-40ºC - 85ºC

Relative Humidity

5 to 95%, 0ºC - 60ºC non-condensing

Shock

Operating

30g peak acceleration, 11 (

±

1)ms pulse width

Non-operating

50g peak acceleration, 11 (

±

1)ms pulse width

Vibration

Tested 5 g @ 10 - 500Hz per IEC 68-2-6

Fiber Optic Cable

Fiber Type

200/230 micron HCS (Hard Clad Silica)

Fiber Termination Type

Versalink V-System

Assemblies

Cable assemblies can be ordered from Allen-Bradley, catalog
number 1403-CFxxx (xxx = length in meters); or from Lucent
Technologies, Specialty Fiber Technologies division.

Maximum Length

300 meters

Minimum Length

1 meter

Power Conductors

Wire Size

12 gauge maximum, 24 gauge minimum (#12 AWG to 24
AWG), stranded

Category

2

(2)

Maximum Length

3 meters