12 GuardPLC Relay Output Module

Rockwell Automation Publication 1753-IN012C-EN-P - June 2010

Relay Outputs

Number of outputs

8 normally open contacts

Switching voltage

5V,

250V AC/250V DC

Switching current

UL:

24V DC @ 1 A noninductive, external fusing adapted

250V AC @ 6 A general purpose

TÜV:

30V DC, 90 W (3.15 A) max, noninductive, external fusing adapted

70V DC, 22 W (0.315 A) max, noninductive, external fusing adapted

127V DC, 25 W (0.25 A) max, noninductive, external fusing adapted

250V DC, 40 W (0.16 A) max, noninductive, external fusing adapted

250V AC, 250 VA, cos

ϕ

0.5 max

250V AC, 625 VA, cos

ϕ

1.0 max

Turn-on time

approx. 30 ms

Turn-off time

approx. 10 ms

Bounce time

approx. 15 ms

Service life, mechanical

10

6

switching cycles

Service life, electrical

2.5 x 10

5

switching cycles with resisitive full load and

0.1 switching cycles

per second

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.