Rockwell Automation 1753-OW8 GuardPLC 8-Relay Output Module Installation Instructions User Manual
Page 12

12 GuardPLC Relay Output Module
Rockwell Automation Publication 1753-IN012C-EN-P - June 2010
Relay Outputs
Number of outputs
8 normally open contacts
Switching voltage
≥
5V,
≤
250V AC/250V DC
Switching current
UL:
•
24V DC @ 1 A noninductive, external fusing adapted
•
250V AC @ 6 A general purpose
TÜV:
•
30V DC, 90 W (3.15 A) max, noninductive, external fusing adapted
•
70V DC, 22 W (0.315 A) max, noninductive, external fusing adapted
•
127V DC, 25 W (0.25 A) max, noninductive, external fusing adapted
•
250V DC, 40 W (0.16 A) max, noninductive, external fusing adapted
•
250V AC, 250 VA, cos
ϕ
≥
0.5 max
•
250V AC, 625 VA, cos
ϕ
≥
1.0 max
Turn-on time
approx. 30 ms
Turn-off time
approx. 10 ms
Bounce time
approx. 15 ms
Service life, mechanical
≥
10
6
switching cycles
Service life, electrical
≥
2.5 x 10
5
switching cycles with resisitive full load and
≤
0.1 switching cycles
per second
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publicat
.
Technical Specifications - 1753-OW8