Environmental Specifications - 1753-OW8

Attribute

1753-OW8

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged nonoperating cold)
IEC 60068-2-2 (Test Bb, Unpackaged nonoperating dry

heat)

IEC 60068-2-14 (Test Na, Unpackaged nonoperating

thermal shock)

-40…85 °C (-40…185 °F)

Temperature, operating

IEC 60068-2-1 (Test Ad, operating cold)
IEC 60068-2-2 (Test Bd, operating dry heat)
IEC 60068-2-14 (Test Nb, operating thermal shock)

0…60 °C (32…140 °F)

Temperature, surrounding air

60 °C (140 °F)

Vibration

IEC 60068-2-6 (Test Fc, operating)

1 g @ 10…150 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, unpackaged shock)

15 g

Relative humidity

IEC 60068-2-30 (Test Db, unpackaged damp heat)

10…95% noncondensing

Emissions

CISPR 11: Group 1, Class A

ESD Immunity

IEC 61000-4-2

6 kV contact discharges

8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3

10V/m with 1kHz sine-wave 80% AM from
80 MHz…2000 MHz

1 V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz

EFT/B Immunity

IEC 61000-4-4

±2 kV @ 5 kHz on DC power ports

±1 kV @ 5 kHz on signal ports

±1 kV @ 5 kHz on communication ports

Surge Transient Immunity

IEC 61000-4-5

±500V line-line (DM) and ±500V line-earth
(CM) on DC power ports

±1 kV line-earth (CM) on signal ports

±1 kV line-earth (CM) on communication ports

Conducted RF Immunity

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz

Damped Oscillatory Wave Immunity

IEC 61000-4-12

±1 kV line-earth (CM) on signal ports

±1 kV line-earth (CM) on power ports

Advertising