8. If the adapter module does not lock in place, use a screwdriver or

similar device to move the locking tab down while pressing the
adapter module flush onto the DIN rail, and release the locking tab to
lock the adapter module in place. If necessary, push up on the locking
tab to lock.

9. Reinstall the module in the adjacent terminal base unit.

Connect Wiring

1. Connect the remote I/O cable to the removable remote I/O

connector.

2. Connect +V dc power to the left side of the lower connector, terminal

A.

3. Connect -V common to the left side of the upper connector, terminal

B.

4. Connections C and D are used to pass +V dc power (D) and -V

common (C) to the next module in the series (if required).

Set the Addressing Mode Switches

1. Lift the hinged switch cover on the front of the adapter to expose the

switches.

2. Set the switches as shown below.
3. Cycle power to the adapter after setting the switches.

8 and 16-point Mode Switch Settings

WARNING

If you connect or disconnect the communications

cable with power applied to this module or any

device on the network, an electrical arc can occur.

This could cause an explosion in hazardous location

installations.

Connect

To terminal

Blue Wire - RIO

1

Shield Wire - RIO

SH

Clear Wire - RIO

2

ATTENTION

If this is the last adapter, you must terminate the

remote I/O link here. Use a terminating resistor

connected across terminals 1 and 2. Refer to your

processor manual for information on the size of the

resistor.

C

Push down and in at the same
time to lock the adapter to the
DIN rail.

When the adapter is locked onto the DIN
rail, gently push the flexbus connector into
the adapter to complete the backplane

20127

1

SH

2

B

D

A

20131_LT

24V

COM

Allen-Bradley

ADAPTER

ACTIVE FAULT

LOCAL
FAULT

Termination resistor (if required)
82 W or 150 W (refer to your
processor documentation for size and usage)

PWR

C

1794-ASBLT

ATTENTION

To reduce susceptibility to noise, power analog

modules and digital modules from separate power

supplies. Do not exceed a total length of 32.8 ft

(10m) for dc power cabling.

ATTENTION

Some switches on this adapter differ from the

switches on previous versions. Make certain that

you identify each switch before setting.

When using this
addressing
mode

And

Mode
Switch 2
S1-1

Mode
Switch 1
S2-5

Mode
Switch 0
S2-8

Standard (as
shipped

8 and/or 16-point
modules

See note
1

ON

ON

Compact

8-point modules

OFF

ON

OFF

16-point modules

ON

ON

OFF

Complementary

See complementary table below.

Primary Chassis

8-point modules

OFF

OFF

ON

Complementary
Chassis

ON

OFF

ON

Complementary

See complementary table below.

Primary Chassis

16-point modules

OFF

OFF

OFF

Complementary
Chassis

ON

OFF

OFF

1

In Standard mode, this switch retains its function as switch position 1 of
rack addressing. In standard mode, the module is functionally

interchangeable with 1794-ASB series A or B adapters.

2

In compact mode, 32-point modules appear as 8 or 16-point modules.

3

When programming block transfers, address analog modules as module 0

if switch S1-1 is on; module 1 if switch S1-1 is off.

8
7
6
5
4
3
2
1

8
7
6
5
4
3
2
1