Specifications mounting dimensions – Rockwell Automation 1794-ASBLT/A FLEX I/O Remote I/O Adapter Installation Instructions User Manual

Page 5

Advertising
background image

5

Publication 1794-IN110A-EN-P - August 2005

Specifications

Mounting Dimensions

(

Specifications - Remote I/O Adapter, Cat. No. 1794-ASBLT/D

I/O Capacity

8 modules

Power Supply

Power supply must be capable of providing a turn-on inrush surge
current of 23 A (at 24V dc) for 2 ms for each adapter connected to
the power supply.

Input Voltage Rating

24V dc nominal
19.2V to 31.2 V dc (includes 5% ac ripple)

Communication Rate

57.6 kbps

115.2 kbps

230 kbps
NOTE: PLC5/15 and PLC5/25 can only support 57.6 kbps

Indicators

Power - green
Adapter Active - green
Adapter Fault - red
Local Fault - red

Flexbus Output Current

640 mA maximum

Isolation Voltage

50V continuous

Tested at 850V dc for 1 s between user power and flexbus

Current Draw

330 mA at 24V dc; 450 mA maximum

Power Dissipation

4.6 W maximum @ 31.2V dc

Thermal Dissipation

Maximum 1.7 BTU/hr @ 31.2V dc

General Specifications

Dimensions

3.4H x 2.7W x 2.7D inches
87H x 69W x 69D mm

Environmental Conditions

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55 °C (32 to 131 °F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
–40 to 85 °C (–40 to 185 °F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating

Damp Heat):
5 to 95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500 Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz

EFT/B Immunity

IEC 61000-4-4:
±2 kV at 5 kHz on power ports

±2 kV at 5 kHz on communications ports

Surge Transient
Immunity

IEC 61000-4-5:
±2 kV line-earth(CM) on communications ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1 kHz sine-wave 80%AM from 150 kHz to 80 MHz

Enclosure Type Rating

None (open-style)

Conductors

Wire Size

Category

1

Communications:

12 AWG (2.5mm2) …22 AWG (0.34mm2) solid or stranded copper
wire rated at 75°C or greater, 3/64 inch (1.2mm) insulation
maximum.

Power:

12 AWG (2.5mm2) …22 AWG (0.34mm2) solid or stranded copper
wire rated at 75°C or greater, 3/64 inch (1.2mm) insulation
maximum."
2 on communication ports

3 on power ports

Terminal Screw Torque

7 pound-inches (0.8 Nm)

Remote I/O Cable

Belden 9463 as specified in publication ICCG-2.2

Remote I/O connector Plug

Part Number 942029-03

Certifications (when
product is marked)

2

C

UL

US

UL Listed Industrial Control Equipment, certified for US

and Canada

C

UL

US

UL Listed for Class I, Division 2, Groups A, B, C and D

Hazardous locations, certified for US and Canada

CSA

CSA certified Process Control Equipment

CSA

CSA certified Process Control Equipment for Class I,

Division 2, Groups A, B, C and D Hazardous locations

CE

European Union 89/336/EEC EMC Directive,

compliant with:

EN 61000-6-4; Industrial Emissions

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

C-Tick Australian Radiocommunications Act compliant with

AS/NZS CISPR 11, Industrial Emissions

1

You use this category information for planning conductor routing as described in Allen-Bradley
publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.

2

For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of

Conformity, Certificates and other certification details.

Inches

(Millimeters)

3.4

(87)

3.2

(80)

2.7

(68)

.83 (21)

1794-ASBLT/D

3.4H x 2.7W x 2.7D
(87H x 68W x 69D)

1.4

(35)

A

2.3

(59)

A

= Mounting hole dimensions for optional wall/panel mounting kit

B

B

= DIN rail

2.0

(50)

1.2

(30)

C

C

= Secure DIN rail approximately every 200mm

1794-ASBLT

Advertising