Configure Your Input Module

Configure your input module by setting bits in the configuration word (write word).

Set the Input Filter Time

To set the input filter time, set the associated bits in the output image table
(complementary word) for the module.

For example, to increase the off-to-on filter time to 4 ms for all inputs at address
rack 1, module group 0, (using 1794-IB32 as an example), set bits and program as
shown below.

Refer to the following Input Filter time chart for other bit settings.

Input Filter Time

Specifications - 24V DC 8 Input Module, Cat. No. 1794-IB8

Specifications - 24V DC 16 Input Module, Cat. Nos. 1794-IB16 and
1794-IB16K

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read 1
(1794-IB16,
1794-IB32)

I15

I14

I13

I12

I11

I10

I9

I8

I7

I6

I5

I4

I3

I2

I1

I0

Read 1
(1794-IB8)

Not used

I7

I6

I5

I4

I3

I2

I1

I0

Read 2
(1794-IB16)

C = Counter Input value of input 15

Read 2
(1794-IB32)

I31

I30

I29

I28

I27

I26

I25

I24

I23

I22

I21 I20 I19 I18 I17 I16

Write 1
(1794-IB8)

Not used

Input Filter
0…07

Write 1
(1794-IB16)

Not used

CF

CR

Not used

Input Filter
12…15

Input Filter
0…11

Write 1
(1794-IB32)

Not used

Input Filter FT
0…31

Not used

Where I = Input

C = Counter value for input 15

FT = Input filter time

CR = Counter reset

CF = Counter fast - where 1 = fast input (raw data), 0 = standard input filtered data

NOTE: C, CR and CF not available when used with any series 1794-ASB or 1794-ASB2 remote I/O adapter
modules.

+V1 COM1

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

NC

+V2 = Terminals 43, 45, 47, and 49

Inputs

+V1 COM1 +V1 COM1 +V1 COM1

+V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC

+V1 = Terminals 35, 37, 39, and 41

COM1 = Terminals 36, 38, 40, and 42

NC = No connections (terminals 16, 33, 34, and 51)

COM2 = Terminals 44, 46, 48, and 50

NC

NC

(1794-TB32 shown)

Inputs

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

FT = 0…7 (1794-IB8)
FT = 0…11 (1794-IB16)

1794-IB16

O:010

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Oct.

FT = 12…15

FT = 0…31
1794-IB32

1

0

0

7

6

5

4

3

FLL

I:000

00

Fill File
Source
Destination
Length

#O:010

1

Write FT to complement

of input module.

Write filter time on system startup.

7

6

5

4

3

2

1

0

0

1

0

= 4 Octal or 4 Decimal

2

1

0

= 44 Octal or 36 Decimal

0

1

0

1

0

0

1794-IB8

1794-IB16

1

0

0

= 4 Octal or 4 Decimal

1

0

0

1794-IB32

09

08

10

11

12

13

14

15

Bits

Description - Filter Time

Filter Time

02

01

00

Inputs 0…07 (1794-IB8)

1794-IB8, -IB16, -IB16K, -IB32

02

01

00

Inputs 0…11 (1794-IB16, -IB16K)

05

04

03

Inputs 12…15 (1794-IB16, -IB16K)

10

09

08

Inputs 0…31 (1794-IB32)

Off to On/On to Off

0

0

0

Filter time 0 (default)

0.25 ms

0

0

1

Filter time 1

0.5 ms

0

1

0

Filter time 2

1 ms

0

1

1

Filter time 3

2 ms

1

0

0

Filter time 4

4 ms

1

0

1

Filter time 5

8 ms

1

1

0

Filter time 6

16 ms

1

1

1

Filter time 7

32 ms

Specification

Description

Number of inputs

8, nonisolated, sinking

Module location

1794-TB3 or 1794-TB3S terminal base unit

On-state voltage, min.

10V DC

On-state voltage, nom.

24V DC

On-state voltage, max.

31.2V DC

On-state current, min.

2.0 mA

On-state current, nom.

8.0 mA

On-state current, max.

12.0 mA

Off-state voltage, max.

5.0V DC

Off-state current, max.

1.5 mA

Input impedance

4.6K

Ω

Isolation voltage

50V (continuous), Basic Insulation Type, between field side and system

No isolation between individual channels

Type tested at 850V DC for 60 s

Flexbus current

20 mA at 5V DC

Power dissipation

3.5W max. @ 31.2V DC

Thermal dissipation

Max. 11.9 BTU/hr @ 31.2V DC

Specification

Description

Number of inputs

16 (1 group of 16), nonisolated, sinking

Module location

1794-TB3 or 1794-TB3S terminal base unit

Mounting

Refer to the derating curve.

On-state voltage, min.

10V DC

On-state voltage, nom.

24V DC

On-state voltage, max.

31.2V DC

On-state current, min.

2.0 mA

On-state current, nom.

8.0 mA

On-state current, max.

12.0 mA

Off-state voltage, max.

5.0V DC

Off-state current, max.

1.5 mA

Input impedance

4.6K

Ω

Isolation voltage

50V (continuous), Basic Insulation Type, between field side and system

No isolation between individual channels

Type tested at 707V DC for 60 s

Flexbus current

30 mA at 5V DC

Power dissipation

6.1W max. @ 31.2V DC

Thermal dissipation

Max. 20.8 BTU/hr @ 31.2V DC

Advertising