General specifications, Environmental specifications, Certifications – Rockwell Automation 1794-IB8_IB16_IB16K_IB32 Flex I/O Digital Input Modules Installation Instructions User Manual

Page 5

Advertising
background image

5

Publication 1794-IN093C-EN-P - December 2009

Specifications - 24V DC 32 Input Module, Cat. No. 1794-IB32

General Specifications

Environmental Specifications

Certifications

Specification

Description

Number of inputs

32 (2 groups of 16), nonisolated within groups, sinking

Module location

1794-TB32 or 1794-TB32S terminal base unit

On-state voltage, min.

19.2V DC

On-state voltage, nom.

24V DC

On-state voltage, max.

31.2V DC

On-state current, min.

2.0 mA

On-state current, nom.

4.1 mA at 24V DC

On-state current, max.

6.0 mA

Off-state voltage, max.

5.0V DC

Off-state current, max.

1.5 mA

Input impedance

6.0K

Ω

Isolation voltage

50V (continuous), Basic Insulation Type, between field side and system

No isolation between individual channels

Routine tested at 2121V DC for 2 s

Flexbus current

25 mA at 5V DC

Power dissipation

6.0W max. @ 31.2V DC

Thermal dissipation

Max. 20.5 BTU/hr @ 31.2V DC

Specification

Description

Input filter time

(1)

Off to On

On to Off

(1)

Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off
filter time is time from the input signal dropping below the valid level to recognition by the module.

0.25 ms, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms

0.25 ms, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms

0.25 ms default - Selectable using configuration word 3

Terminal base screw torque

Determined by installed terminal base.

Dimensions (HxWxD, with
module installed)

94 x 94 x 69 mm

(3.7 x 3.7 x 2.7 in.)

Indicators (field side indication,
customer device driven)

1794-IB8: 8 yellow status indicators

1794-IB16, -IB16K: 16 yellow status indicators

1794-IB32: 32 yellow status indicators

External DC power

Supply voltage, nom.

Voltage range

24V DC

1794-IB8, -IB16, -IB16K: 10…31.2V DC (includes 5% AC ripple)

1794-IB32: 19.2…31.2V DC (includes 5% AC ripple)

North American temp code

1794-IB8 and -IB32: T3C; 1794-IB16 and -IB16K: T4A

IEC temp code

1794-IB8: T3; 1794-IB16 and -IB16K: T4

Specification

Description

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…55 °C (32…131 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

–40…85 °C (–40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

4 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz (all)

10V/m with 200 Hz 50% pulse 100% AM at 900 MHz (all)

10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz (1794-IB8, -IB16,
and -IB16K)

1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz (1794-IB8)

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz (1794-IB16,
-IB16K, and -IB32)

EFT/B immunity

IEC 61000-4-4:

±2kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5:

±1kV line-line (DM) and ±2kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Enclosure type rating

None (open-style)

Wire size

Determined by installed terminal base.

Wiring category

(1)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

2 - on signal ports

Certifications (when product
is marked)

(1)

(1)

See the Product Certification link at

www.ab.com

for Declarations of Conformity, Certificates and other certification

details.

Description

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See
UL File E65584.

UL Listed for Class I, Division 2, Group A, B, C, D Hazardous Locations,
certified for US and Canada. See UL File 194810.

CSA

(for 1794-IB8, -IB16, and -IB16K)

CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2, Group A,
B, C, D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act compliant with:

AS/NZS CISPR 11; Industrial Emissions

Ex

(for 1794-IB8, -IB16, and -IB16K)

European Union 94/9/EC ATEX Directive, compliant with:

EN 60079-15; Potentially Explosive Atmospheres, Protection “n”

EN 60079-0; General Requirements

II 3 G Ex nA IIC T3 X (1794-IB8)

II 3 G Ex nA IIC T4 X (1794-IB16, -IB16K)

TÜV

(for 1794-IB16)

TÜV Certified for Functional Safety:

up to and including SIL 2

Advertising