Rockwell Automation 1747-ACNR15 ControlNet Adapter Module Installation Instructions User Manual
Page 15
 
ControlNet Adapter Module 15
Publication 1747-IN017C-EN-P - May 2001
Solid Red
FATL Number
Number
Module is not 
communicating.
The adapter has either failed 
a hardware test, or gone into 
a state from which it cannot 
recover. The two numbers 
following the FATL describe 
the problem in detail.
Document the two numbers. 
Power cycle the adapter. 
Contact Technical Support at 
440.646.6800.
Flashing Red A#00 ERR
Module is not 
communicating.
The node address switches 
are set to 00 which is not 
valid.
Power the adapter off, 
remove the adapter from the 
chassis, change the node 
address switch to something 
other than 00, replace the 
adapter in the chassis, and 
apply power.
Flashing Red DUP NODE
Module is not 
communicating.
The adapter has detected a 
duplicated node address on 
the network.
Correct the duplicate node 
address problem.
Flashing Red CPU OVER
Module is not 
communicating.
The ControlNet configuration 
has overloaded the central 
processing unit in the 
adapter.
Reduce load on adapter by 
removing some connections 
or increasing the connection 
RPI values.
Flashing 
Green
IDLE
Module is working 
properly, but there 
are no active 
connections.
None
None
Flashing 
Green
NET ERR
Module is not 
communicating.
The adapter has detected a 
cable fault and is attempting 
to recover. The adapter is 
sending the three “I’m 
alive!” packets.
None, check cable if problem 
persists.
Solid Green
ACTV A#XX
Module is working 
properly.
None
None
Solid Green
BOOT A#XX
Module is on 
network, but not 
supporting any 
connections.
The main code in the module 
has failed, or the main code 
is being updated.
Update the main code with 
the latest Series and 
Revision code.
Off
CODE UPDT 
A#XX
Firmware update 
mode.
Adapter firmware is being 
updated via ControlFlash 
update utility.
None
OK LED
Display
Description
Probable Cause
Recommended Action