Rockwell Automation 1734-EP24DC Point I/O Expansion Power Supply Installation Instructions User Manual
Page 18

18 POINT I/O 24V dc Expansion Power Supply
Publication
1734-IN058B-EN-P - June 2005
Emissions
CISPR 11: Group 1, Class A
ESD Immunity
IEC6100-4-2
6 kV contact discharges
8 kV air discharges
Radiated RF Immunity
IEC 61000-4-3
10V/m with 1 KHz sine-wave 80% AM
from 30 MHz to 2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
EFT/B Immunity
IEC 61000-4-4
+4 kV at 2.5 kHz on power ports
Surge Transient Immunity
IEC 61000-4-5
+1 kV line-line (DM) and + 2kV line-earth (CM)
on power ports
Conducted RF Immunity
IEC61000-4-6
10Vrms with 1 kHz sine-wave 80% AM
from 150 kHz to 80 MHz
Enclosure Type Rating
None (open-style)
Conductor Size
#22…#14 AWG (0.324…2.08 sq. mm)
solid or stranded copper wire rated @ 75 °C or greater
3/64 inch (1.2 mm) insulation maximum
Conductor Category
1
1 - on power ports
1
Use this Conductor Category information for planning conductor routing. Refer to publication
1770-4.1, Industrial Automation Wiring and Grounding Guidelines.
Environmental Specifications