Rockwell Automation 1734-OE4C Installation Instructions User Manual
Page 13

POINT I/O 4 Channel Analog Current Output Module 13
Publication
1734-IN034B-EN-P - November 2010
Default Data Map for the 1734-OE4C Analog Output Module
Message size: 4 Bytes
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Produces
(scanner
Rx)
High Byte - Channel 1 Status
Low Byte - Channel 0 Status
Not used
H
C
A
L
C
A
C
M
C
F
Not used
H
C
A
L
C
A
C
M
C
F
High Byte - Channel 3 Status
Low Byte - Channel 2 Status
Not used
H
C
A
L
C
A
C
M
C
F
Not used
H
C
A
L
C
A
C
M
C
F
Where:
CF = Channel Fault status; 0 = no error, 1 = fault
CM = Calibration Mode; 0 = Normal, 1 = calibration mode
LCA = Low Clamp Alarm; 0 = no error, 1 = fault
HCA = High Clamp Alarm; 0 = no error, 1 = fault
Message size: 8 bytes
15
14
13
12
11
10
09
08
0
7
0
6
0
5
0
4
0
3
0
2
0
1
0
0
Consumes
(scanner Tx)
Output Channel 0 High Byte
Output Channel 0 Low Byte
Output Channel 1 High Byte
Output Channel 1 Low Byte
Output Channel 2 High Byte
Output Channel 2 Low Byte
Output Channel 3 High Byte
Output Channel 3 Low Byte