Specifications – Rockwell Automation 1734-OE4C Installation Instructions User Manual
Page 17

POINT I/O 4 Channel Analog Current Output Module 17
Publication
1734-IN034B-EN-P - November 2010
Specifications
Output Specifications
Attribute
Value
Number of outputs
4 analog, single-ended, non-isolated
Resolution current
16 bits - over 0…21mA
0.32
μ
A/cnt)
Output current terminal
0 mA output until communication established
4…20 mA user configurable
0…20 mA user configurable
Absolute accuracy
(1)
current
terminal, min
(1)
Includes offset, gain, non-linearity and repeatability error terms
0.4% (0.1% if calibrated)
Accuracy drift
w/temperature current
terminal
<50 ppm/°C
Resistive load on mA output
0…750
Ω
Conversion type
Digital to analog converter
Conversion rate
1
μ
s
Data format
Signed Integer
Calibration
Factory calibrated
Step response to 63% of FS
40
μ
s
Surge current
2 A for 10 ms, repeatable every 3 s
Status indicators
1 green/red network status indicator, logic side
1 green/red module status indicator, logic side
4 green/red output status indicators, logic side
IMPORTANT
Refer to Publication
for information on breaking the field power
distribution bus. Refer to sections “When to Use the Field Power
Distributor” and “When to Use the Expansion Power Unit”.