Connecting wiring – Rockwell Automation 1794-APB/B FLEX I/O PROFIBUS Adapter Module Installation Instructions User Manual

Page 3

Advertising
background image

3

Publication 1794-IN087C-EN-P - July 2005

5. Release the locking tab (C) and remove the adapter module.
6. Before installing the new adapter, notice the notch on the right rear of

the adapter. This notch accepts the hook on the terminal base unit.
The notch is open at the bottom. The hook and adjacent connection
point keep the terminal base and the adapter tight together, reducing
the possibility of a break in communication over the backplane.

7. Complete the adapter mounting as shown below.

8. Reinstall the module in the adjacent terminal base unit.

Connecting Wiring

1. Connect the PROFIBUS drop cable to the 9-pin D-shell connector

according to the following pin assignments.

.

2. Connect the cable shield to Pin 1. The shield is connected to earth

ground.

3. Connect the data signal pins on both ends (signal + pin3 and signal -

pin 8).

4. Insert the wired connector into the mating connector on the adapter.

5. Connect +V dc power to the left side of the lower connector, terminal

E.

6. Connect -V common to the left side of the upper connector, terminal

D.

7. Connections G and F are used to pass +V dc power (G) and -V

common (F) to the next module in the series (if required).

Pin

RS-485
Reference

Signal

Description

1

Shield

Shield, RC to earth ground

2

RP

Not used

3

B/B’

RXD/TXD-P

Receive/transmit data - P

4

CTNR-P

Not used

5

C/C’

DGND

Data Ground

6

VP

Voltage plus (+5V)

7

RP

Not used

8

A/A’

RXD/TXD-N

Receive/transmit data - N

9

CTNR-N

Not used

Metal Shell

Earth Ground

C

Flexbus connector

C

Push down and in at the same time to lock the adapter to the DIN rail.

When the adapter is locked onto the DIN rail, gently push the flexbus connector
into the adapter to complete the backplane

If the adapter does not lock in place, use a screwdriver or similar device to move the
locking tab down while pressing the adapter flush onto the DIN rail, and release the
locking tab to lock the adapter module in place. If necessary, push up on the locking
tab to lock.

ATTENTION

V dc power wiring should be less than 3 m (9.8 ft).

ATTENTION

When connecting wiring, torque terminal screws D,

E, F, and G to 7 pound-inches (0.8 Nm).

1

.

.

+ 5 V

Data Ground

Signal +

Shield

Pin #1

5

RCV/ Xmit Data +

9

6

.

.

DROP CABLE

1 MW

PROFIBUS

ADAPTER

Pin #3

Pin #5

Pin #6

Signal - Pin #8

Earth Ground

0.01

µ F

500V dc

RCV/ Xmit Data -

D

F

G

E

20131

24V

COM

PROFIBUS Connector