Specifications, Mounting dimensions – Rockwell Automation 1794-APB/B FLEX I/O PROFIBUS Adapter Module Installation Instructions User Manual

Page 5

Advertising
background image

5

Publication 1794-IN087C-EN-P - July 2005

Specifications

Mounting Dimensions

Specifications - PROFIBUS Adapter Cat. No. 1794-APB/B

I/O Capacity

8 modules

Input Voltage Rating

24V dc nominal
19.2V to 31.2 V dc (includes 5% ac ripple)

Input Current

450 mA maximum, 330 mA at 24V dc

Inrush Current

23 A for 2 ms

Communication Rate

All rates up to 12.0 Mbits/s

Indicators

Status- red/green
PROFIBUS- red/green

Flexbus Output Current

640 mA maximum

Isolation Voltage

Tested at 850V dc for 1s between user power and flexbus

Power Dissipation

7.68 W maximum @ 19.2V dc

Thermal Dissipation

Maximum 26 BTU/hr @ 19.2V dc

Dimensions

3.4H x 2.7W x 2.7D inches
87H x 69W x 69D mm

Environmental Conditions

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55 °C (32 to 131 °F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
–40 to 85 °C (–40 to 185 °F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):
5 to 95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500 Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10 V/m with 1kHz sine-wave 80%AM from 30 MHz to 1000 MHz

EFT/B Immunity

IEC 61000-4-4:
±2 kV at 5 kHz on communication ports

Surge Transient
Immunity

IEC 61000-4-5:
±2 kV line-earth (CM) on shielded ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1 kHz sine-wave 80%AM from 150 kHz to 30 MHz

Enclosure Type Rating

None (open-style)

Power Conductors

Wire Size

Category

1

12 AWG (2.5 mm

2

) stranded copper wire rated at 75 °C or higher

3/64 inch (1.2 mm) insulation maximum
2

Terminal Screw Torque

7 pound-inches (0.8 Nm)

PROFIBUS Cable

Standard drop cable

PROFIBUS connector Plug

9-pin D-shell

Certifications (when
product is marked)

2

C

-UL-

US

UL Listed for Class I, Division 2, Groups A, B, C and D

Hazardous locations, certified for US and Canada

CE

European Union 89/336/EEC EMC Directive,

compliant with:

EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity

C-Tick Australian Radiocommunications Act compliant with

AS/NZS CISPR 11, Industrial Emissions

Publications

User Manual 1794-UM059

1

You use this category information for planning conductor routing as described in Allen-Bradley
publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.

2

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other

certification details.

Inches

(Millimeters )

3.4

(87)

3.2

(80)

2.7

(68)

.83 (21)

1794-APB/B

3.4H x 2.7W x 2.7D

(87H x 68W x 69D)

1.4

(35)

A

2.3

(59)

A

= Mounting hole dimensions for optional mounting kit

B

B

= DIN rail

2.0

(50)

1.2

(28)

C

C

= Secure DIN rail approximately every 200mm

24V DC

Adapter

PROFIBUS

Advertising