DeviceNet ArmorBlock Network Powered 8-input/8-output Module 13

Publication

1732D-IN010A-EN-E - April 2009

Indicator

Status

Description

Network
status

Off

Device is not online.

- Device has not completed dup_MAC-id test.

- Device not powered – check module status indicator.

Green

Device operating normally and is online with
connections in the established state. As a Group 2
module, it means that the module is allocated to a
master.

Flashing green

Device is online with no connections in the established
state.

Red

Critical link failure – failed communications module.

Flashing red

Recoverable fault – an I/O connection has timed out.

Module
status

Off

No power applied to the device.

Green

Device is operating normally.

Flashing green

Device needs commissioning due to missing,
incomplete, or incorrect configuration.

Flashing red

Recoverable fault – input or output short circuit.

Red

Critical fault – Device timed out or has an
unrecoverable fault.

I/O status

Off

Output is not energized or input is not valid.

Yellow

Output is energized or input is valid.