Rockwell Automation 1732D-8I8O1212D DNet ArmorBlock Network Powered 8-input/8-output Module IN User Manual
Page 13

DeviceNet ArmorBlock Network Powered 8-input/8-output Module 13
Publication
1732D-IN010A-EN-E - April 2009
Indicator
Status
Description
Network
status
Off
Device is not online.
- Device has not completed dup_MAC-id test.
- Device not powered – check module status indicator.
Green
Device operating normally and is online with
connections in the established state. As a Group 2
module, it means that the module is allocated to a
master.
Flashing green
Device is online with no connections in the established
state.
Red
Critical link failure – failed communications module.
Flashing red
Recoverable fault – an I/O connection has timed out.
Module
status
Off
No power applied to the device.
Green
Device is operating normally.
Flashing green
Device needs commissioning due to missing,
incomplete, or incorrect configuration.
Flashing red
Recoverable fault – input or output short circuit.
Red
Critical fault – Device timed out or has an
unrecoverable fault.
I/O status
Off
Output is not energized or input is not valid.
Yellow
Output is energized or input is valid.