Connect the i/o cord sets to the module, Network connector, M12-style input connectors i/o connector – Rockwell Automation 1732D-8I8O1212D DNet ArmorBlock Network Powered 8-input/8-output Module IN User Manual
Page 9: M12-style 5-pin female input connector

DeviceNet ArmorBlock Network Powered 8-input/8-output Module 9
Publication
1732D-IN010A-EN-E - April 2009
Connect the I/O Cord Sets to the Module
The ArmorBlock DeviceNet family has 5-pin micro-style connectors.
We provide caps to cover the unused connectors on your module.
Connect the quick-disconnect cord sets that you selected for your module to
the appropriate ports.
Network Connector
Refer to the pinout diagram for the network connector.
M12-style Input Connectors
I/O Connector
Refer to the pinout diagram for the I/O connector.
M12-style 5-pin Female Input Connector
Male
Female
(View into Connector)
Pin 1
Drain
Pin 2
V+ (Red)
Pin 3
V- (Black)
Pin 4
CAN_H (White)
Pin 5
CAN_L (Blue)
41452
44175
(View into Connector)
Pin 1
Sensor Source Voltage
Pin 2
Output
Pin 3
Return
Pin 4
Input
Pin 5
PE
41452