Publication 1746-IN027D-EN-P - December 2012
Input Modules Heat Dissipation
Catalog Numbers
Watts per Point
Minimum Watts
Total Watts
1747-IA4
0.27
0.175
1.30
1746-IA8
0.27
0.250
2.40
1746-IA16
0.27
0.425
4.80
1746-IB8
0.20
0.250
1.90
1746-IB16
0.20
0.425
3.60
1746-IC16
0.22
0.425
3.95
1746-IG16
0.02
0.700
1.00
1746-IH16
0.32
0.217
5.17
1746-IM4
0.35
0.175
1.60
1746-IM8
0.35
0.250
3.10
1746-IM16
0.35
0.425
6.00
1746-IN16
0.35
0.425
6.00
1746-ITB16
0.20
0.425
3.60
1746-ITV16
0.20
0.425
3.60
1746-IV8
0.20
0.250
1.90
1746-IV16
0.20
0.425
3.60
Output Modules Heat Dissipation
Catalog Numbers
Watts per Point
Minimum Watts
Total Watts
1746-OA8
1.000
0.925
9.00
1746-OA16
0.462
1.850
9.30
1746-OAP12
1.000
1.850
10.85
1746-OB6EI
0.440
0.230
2.90
1746-OB8
0.775
0.675
6.90
1746-OB16
0.388
1.400
7.60
1746-OB16E
0.150
0.675
3.07
1746-OBP8
0.300
0.675
3.08
1746-OBP16
0.310
1.250
6.26
1746-OG16
0.033
0.900
1.50