Ac input modules – Rockwell Automation 1746-XXXX SLC 500 Digital I/O Modules Installation Instructions User Manual
Page 32

32 SLC 500 Digital I/O Modules
Publication 1746-IN027D-EN-P - December 2012
AC Input Modules
Specifications – 1746-IA4, 1746-IA8, and 1746-IA16
Attribute
Value
1746-IA4
1746-IA8
1746-IA16
(2)
(2)
Removable terminal block.
Voltage category
100/120V AC signal input
Number of inputs
4
8
16
Points per common
4
8
16
Voltage, operating
85...132V AC @ 47...63 Hz
Backplane current consumption
5V DC
0.035 A
0.050 A
0.085 A
24V DC
0.0 A
Signal delay, max
On = 35 ms
Off = 45 ms
Off-state voltage, max
30V AC
Off-state current, max
2 mA
Input current
12 mA @ 120V AC, nom
Inrush current, max
(1)
(1)
An AC input device must be compatible with SLC 500 input circuit inrush current. A current limiting resistor can be used to limit
inrush current; however, the operating characteristics of the AC input-circuit will be affected.
0.8 A
Inrush current time duration, max
0.5 ms
Specifications – 1746-IM4, 1746-IM8, and 1746-IM16
Attribute
Value
1746-IM4
1746-IM8
1746-IM16
(2)
Voltage category
200/240V AC signal input
Number of inputs
4
8
16
Points per common
4
8
16
Voltage, operating
170...265V AC @ 47...63 Hz
Backplane current consumption
5V DC
0.035 A
0.050 A
0.085 A
24V DC
0.0 A
Signal delay, max
On = 35 ms
Off = 45 ms
Off-state voltage, max
50V AC
Off-state current, max
2 mA