Connecting Wiring to the Output Module
Connections to the output module are made to the field wiring arm
(cat. no. 1771-WH) shipped with the module. An optional fused
wiring arm is available (cat. no. 1771-WHF) which provides
individual fusing for each circuit. Attach the wiring arm to the pivot
bar on the bottom of the I/O chassis. The wiring arm pivots upward
and connects with the module so you can install or remove the
module without disconnecting the wires.
You must supply ac (L1) at terminals A through D on the wiring
arm. You need four ac connections to accommodate the total
required surge rating on the module without overstressing any single
connection on the field wiring arm. Jumper all ac (L1) connections
together to prevent module damage.
Figure 2
Connection Diagram
Terminal A
Terminal B
Terminal C
Terminal D
(Actual wiring runs in this direction.)
Terminal E
L1
24V ac
ac Low
Output 00
Output 01
Output 02
Output 03
Output 04
Output 05
Output 06
Output 07
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
Output 17
L2
Output
Device
A
B
C
D
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
E
10674ĆI