Important: You can use an AC (24V) Output Module (cat. no.
1771-OND) to directly drive terminals on an AC (24V)
Input Module (cat. no. 1771-IND) (Figure 3). You can
also use a 1771-OND Output module to drive an AC
(24V) Input Module (cat. no. 1771-IN) but you must
connect a 250 ohm, 5W resistor between the output
terminal and L2 (common) as shown in Figure 3. Use
the same ac power source to power both modules to
ensure proper phasing and prevent module damage.
Figure 3
Driving an Input Module with an Output Module
Note: 1771ĆOND output voltage
range is 10Ć60V ac. However, the
onĆstate voltage range of the
1771ĆIND is 19Ć29V ac.
L1
24V ac High
L2
ac Low
(Cat. No. 1771ĆIN)
Note: 1771ĆOND output voltage
range is 10Ć60V ac. However, the
onĆstate voltage range of the
1771ĆIN is 12Ć28V ac.
L2
ac Low
250 ohm 5W
resistor
L1
24V ac High
L2
AC (24V)
Input Module
AC (24V)
Output Module
(Cat. No. 1771ĆOND)
AC (24V)
Input Module
(Cat. No. 1771ĆIND)
AC (24V)
Output Module
(Cat. No. 1771ĆOND)