5Ć1

5.0 DIAGNOSTICS AND

TROUBLESHOOTING

This section explains how to troubleshoot the module and field

connections.

5.1

Incorrect Data

Problem: The data is either always off, always on, or different than

expected. The possible causes of this are a module in the wrong slot,

a programming error, or a malfunctioning module. It is also possible

that the input is either not wired or wired to the wrong device. Use the

following procedure to isolate the problem:
Step 1.

Verify that the input module is in the correct slot and, for

DCS 5000/AutoMax systems, that the I/O definitions are

correct.
Verify that the slot number being referenced agrees with

the slot number of the module. In DCS 5000/AutoMax

systems, this module's register number is always zero.

Verify that the bit number refers to the proper bit. Note that

the bit number and the wire number are not the same.
For remote I/O installations (DCS 5000/AutoMax systems

only), also verify that the master slot and remote drop

number are defined correctly.

Step 2.

Verify that the input is wired to the correct device.
Confirm that all connections at the terminal strip are tight.

Connect a voltmeter to the proper points on the terminal

strip and toggle the device. The voltmeter should alternate

between 0 and 24 volts. If this does not happen, there is a

problem with either the external device, the power supply,

or the wiring to the terminal strip.
Check the cable for continuity between the faceplate

connector and the terminal strip.

Step 3.

Verify that the module can be accessed.
Connect the programming terminal to the system and run

the ReSource Software. Use the MONITOR I/O function in

DCS 5000/AutoMax systems or the POINT MONITOR

function in AutoMate systems. Toggle the input device to

determine whether the bit is changing state.
If the programmer is able to read the input, the problem

lies in the application software (proceed to step 4). If the

programmer cannot read the inputs, the problem lies in

the hardware (proceed to step 5).

Step 4.

Verify that the user application program is correct.
For DCS 5000/AutoMax systems, verify that the application

program that references the symbolic names associated

with the module has declared those names COMMON (or

global for AutoMax Programming Executive version 4.0

and later ladder tasks) in application tasks.
Verify that the symbolicname in question is being

referenced in the application program. This can be done