Connect the cordset to the flexarmor module – Rockwell Automation 1798-OE2 FlexArmor Analog Output Module User Manual
Page 5

FlexArmor Analog Output Module 5
Publication 1798-IN009A-EN-P - April 2002
4. Screw down the module retaining screws to ensure IP67
compliance.
Connect the Cordset to the FlexArmor Module
The module uses 5 pin micro (12mm) style PCB mounted connectors.
Two micro caps cover the I/O connectors on the module. Remove
the caps and connect your cables to the appropriate ports. Keep the
caps in place on any unused connector to maintain the IP67 rating.
A pinout diagram for the connectors is shown below.
IMPORTANT
•
Torque the screws to 0.5-0.7 Nm. (4.43 - 6.2
inch pounds).
•
Dust caps must have 4 inch pounds of torque
to maintain IP67 compliance.
ATTENTION
!
•
Make sure all connectors and caps are
securely tightened to properly seal the
connections against leaks and maintain IP67
requirements.
•
For maximum noise immunity, input and
output cable return wires must be properly
terminated. When inputs and outputs are
connected in loopback, return wires should
be connected together.
•
I/O cable length should be less than 30
meters.
42652
Female Input Micro-Connector
(View into Socket)
Pin 1 Sensor Power
Pin 2 Current Output
Pin 3 Sensor Common
Pin 4 Voltage Output
Pin 5 Not Used