Connect the cordset to the flexarmor module – Rockwell Automation 1798-OE2 FlexArmor Analog Output Module User Manual

Page 5

Advertising
background image

FlexArmor Analog Output Module 5

Publication 1798-IN009A-EN-P - April 2002

4. Screw down the module retaining screws to ensure IP67

compliance.

Connect the Cordset to the FlexArmor Module

The module uses 5 pin micro (12mm) style PCB mounted connectors.

Two micro caps cover the I/O connectors on the module. Remove
the caps and connect your cables to the appropriate ports. Keep the
caps in place on any unused connector to maintain the IP67 rating.

A pinout diagram for the connectors is shown below.

IMPORTANT

Torque the screws to 0.5-0.7 Nm. (4.43 - 6.2
inch pounds).

Dust caps must have 4 inch pounds of torque
to maintain IP67 compliance.

ATTENTION

!

Make sure all connectors and caps are
securely tightened to properly seal the
connections against leaks and maintain IP67
requirements.

For maximum noise immunity, input and
output cable return wires must be properly
terminated. When inputs and outputs are
connected in loopback, return wires should
be connected together.

I/O cable length should be less than 30
meters.

42652

Female Input Micro-Connector

(View into Socket)

Pin 1 Sensor Power
Pin 2 Current Output
Pin 3 Sensor Common
Pin 4 Voltage Output
Pin 5 Not Used