Troubleshooting with the indicators, Specifications – Rockwell Automation 1798-OE2 FlexArmor Analog Output Module User Manual

Page 6

Advertising
background image

6 FlexArmor Analog Output Module

Publication 1798-IN009A-EN-P - April 2002

Troubleshooting with the Indicators

The following table describes the status indicator on the analog

output modules.

Specifications

I/O Status Indicators

Function Indicator

Status

Fault
LED

Red
Off

Sensor Power Short
Normal

Specifications - 1798-OE2 Analog Output Module

Module Type

Analog Output

Number of Channels

2 single-ended, non-isolated

Resolution

Bits
Voltage/Cnt
Current/Cnt

12 + sign
2.56 mV
5.13 uA

Data Format

16 bit; 2’s complement; left-justified

Conversion Type

Pulse width modulation

Conversion Rate

1.024 ms - All channels

Current Terminal

4-20 mA; 0-20 mA (0 mA output until the module is
configured)

Voltage Terminal

±10V; 0-10V - 3 mA maximum (0V output until the
module is configured)

Step Response to 63% of FS

24 mS

Output Load on Voltage

3 mA maximum

Resistive Load on mA
Output

15-750 ohms

Absolute Accuracy

Voltage Terminal
Current Terminal

0.133% FS @ 25°C
0.425% FS @ 25°C

Accuracy Drift

Voltage Terminal
Current Terminal

0.0045% FS per°C
0.0069% FS per°C

Calibration

None Required

FlexBus Current

10 mA maximum

Power dissipation

2.5W @ 28.8V dc

Sensor Source Current
(per connector)

50 mA

Thermal Dissipation

8.5 BTU/hr @ 28.8V dc

Indicator

1 fault LED Indicator - red

External DC Power

Voltage (24V dc nom.)
Current

10-28.8V dc; 5% AC ripple
85 mA @ 24V dc