Rockwell Automation 61C350 2-In/2-Out 0-10 Volt Analog Rail Module User Manual
Page 18

3Ć4
Channel
Terminal
Number
Terminal Label
Signal
0
1
2
3
VĆOUT
Common
(no label)
0Ć10V+ output
common
(shield; no connection)*
1
4
5
6
VĆOUT
Common
(no label)
0Ć10V+ output
common
(shield; no connection)*
2
7
8
9
VĆIN
Common
(no label)
0Ć10V+ input
common
(shield; no connection)*
3
10
11
12
VĆIN
Common
(no label)
0Ć10V+ input
common
(shield; no connection)*
*This pin makes no electrical connection to the Analog Rail printed circuit board.
Step 10. For the two output channels, connect a shield wire from
the external hardware to the third terminal (terminals 3
and 6, respectively). Insert a jumper between terminals 2
and 3, and between 5 and 6. The shield wire at the
external hardware end of the cable should be cut short
and taped back to prevent any electrical contact. See
figure 3.2.
Step 11. For the two input channels, connect a shield wire from the
external hardware to the third terminal (terminals 9 and
12, respectively). The shield wire at the external hardware
end of the cable should be connected to the source
reference point. See figure 3.2.