Rockwell Automation 61C350 2-In/2-Out 0-10 Volt Analog Rail Module User Manual
Page 19

3Ć5
Channel 0
Channel 1
Channel 2
Channel 3
-
+
I
Load
VĆOut
Common
1
2
3
-
+
I
Load
VĆOut
Common
4
5
6
+
-
I
Source
VĆIn
Common
7
8
9
+
-
I
Source
VĆIn
Common
10
11
12
Figure 3.2 Ć Typical Recommended Input and Output Shielding Methods
Step 12. Turn off power to the Reliance device that will be
connected to the Analog Rail module.
Step 13. Set the Mode" switch on the faceplate of the module to
the desired position.
Step 14. Connect the I/O Rail cable between the Analog Rail
connection labeled Input" and an I/O port on the
Reliance device that will communicate with the module.
Turn on power to the Reliance device that will
communicate with the module. Recall that the Mode
switch is read each time the Reliance device connected
to the Analog Rail module is powered up.
Step 15. The Analog Rail installation is now ready for testing.
Inspect all work to assure that the installation has been
performed properly.
Step 16. Turn on power to the Input Power" wiring. Turn on power
to the external hardware.
Step 17. Verify that the hardware has been installed correctly.
Before testing, insure that the external hardware will not
respond to output signals from the Analog Rail module.