Install swing-out latch bracket, Install units – Rockwell Automation 2193FZ Feeder Circuit Breaker Units Secure Support Pan and ChangeDoor Latch User Manual

Page 8

Advertising
background image

8

Rockwell Automation Publication 2100-IN092A-EN-P - April 2013

Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch

Install Swing-out Latch

Bracket

The swing-out latch bracket installs in the slot in the right-hand unit support of

the Feeder unit compartment. Follow these steps to install the swing-out latch

bracket.

1. Working from the inside of the vertical wireway cutout, place the swing-

out latch bracket on the back of the front flange of the right hand unit

support.

2. Align the latch bracket with the slot in the right hand unit support so that

the alignment tab of the bracket is resting on the bottom of the slot.

3. Working from the inside of the vertical wireway, tighten

the two 10-32 self tapping screws to 32 lb•in (3.6 N•m) to secure the

swing-out latch bracket to the right hand unit support.

Install Units

Follow these steps to install the units.

IMPORTANT

There are no holes in the right-hand unit support for these screws. The two
screws ‘clamp’ the latch to the right-hand unit support.

Tighten to 32 lb•in (3.6 N•m)

ATTENTION: De-energize all units before installing or removing.
When installing or removing MCC units, when possible, de-energize, lockout, and
tag-out all sources of power to the MCC. If the MCC units are installed or removed
with power applied to the main power bus, follow established electrical safety

work practices. Refer to the NFPA 70E Standard for Electrical Safety in the
Workplace publication.
Review your company safety lockout and tag-out procedure.
If power sources are connected to the motor control center, use extreme caution
when inserting units. All buses and the line sides of the inserted units are
energized, and contact with these parts can cause injury or death.
All covers and doors must be in place before applying power to the MCC. If units are
removed, they must be replaced with the appropriate items, such as units, doors,
and unit support pans.

Advertising