2085-irt4 – Rockwell Automation 2085 Micro800 Discrete and Analog Expansion I/O Modules User Manual
Page 47

Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
39
Configure Your Expansion I/O Module Chapter 5
2085-IRT4
For the RTD and Thermocouple expansion I/O, 2085-IRT4, you can configure
sensor type, data format, temperature units, and other properties, on each of the
four individual channels.
Configuration Parameters for 2085-IRT4
Configuration Property
What to do
Description
Enable channel
Click the box to enable.
This parameter enables the particular
channel for operation.
Sensor Type
Select from the following
sensors:
• 100
Ω Platinum 385
• 200
Ω Platinum 385
• 100
Ω Platinum 3916
• 200
Ω Platinum 3916
• 100
Ω Nickel 618
• 200
Ω Nickel 618
• 120
Ω Nickel 672
• 100
Ω Copper 427
• 0…500 Ohm
• 0…100 mV
• Thermocouple B
• Thermocouple C
• Thermocouple E
• Thermocouple J
• Thermocouple K
• Thermocouple TXK/XK (L)
• Thermocouple N
• Thermocouple R
• Thermocouple S
• Thermocouple T
Defines the RTD or Thermocouple sensor
type for the channel.