Receiver Model Numbers:

42GRR--9500, 42GRR--9500--QD, 42GRR--9500--QD1

Hazardous (Classified) Location

(See Note 1)

Hazardous (Classified) or Nonhazardous Loca-

tion

(See Note 2)

Photoelectric Sensors

Zener Diode Barriers

Power Supply &

Load Circuits

A--B #897H--S214

Cable

Brown (Pin 1)

(Pin 4)

Blue

(Pin 3)

Black

Receiver PNP Output Wiring

4

3

Barrier Bus

Power Supply

Sinking PLC Input

24V DC Nom.

( + )

Signal

Return

( -- )

Supply Return

8.5mA Max.

Earth Ground

(less than 1Ohm)

2

1

Receiver Model Numbers:

42GRR--9500, 42GRR--9500--QD, 42GRR--9500--QD1

A--B #897H--S150

A--B #897H--S150

Cable

Brown

Blue

White

(Pin 1)

(Pin 2)

(Pin 3)

3

3

Barrier Bus

Earth Ground

(less than 1Ohm)

1

1

Power Supply

Sourcing PLC Input

24V DC Nom.

( + )

Load

Supply

( -- )

Supply and Signal Return

15mA

Max.

24V DC Nom.

( + )

5V DC Nom.

( + )

TTL

Device

Receiver NPN Output Wiring

Light Source Model Numbers:

42GRL--9540, 42GRL--9540--QD, 42GRL--9540--QD1

A--B #897H--S120

Cable

Brown

Blue

(Pin 1)

(Pin 3)

3

Barrier Bus

Earth Ground

(less than 1Ohm)

1

Supply Return

Power Supply

24V DC Nom.

( + )

( -- )

Light Source Wiring

Table 1: Entity Parameters

Sensor

Barrier

Vmax

31.5V

Vt

Imax

150mA

It

Pmax

0.95W

Pt

Ci

0F

Ca

Li

0mH

La

Notes

:

1. Class I; Division 1, Group A, B, C, D. Class I; Division 2, Group A, B, C, D.
2. Class I; Division 2, Group A, B, C, D if equipment and installation is per national standards.
3. Division 2 applications without the use of a barrier must be installed in accordance with the NEC and CEC.
4. Safety barriers are not required for Class I, Division 2 Group A, B, C, D non-incendive installations when installed per the CEC.
5. Entity parameters of Safety Barriers must match Table 1. Cable values for capacitance and inductance must be added to Ci and Li

values.

6. In Division 2 installations without barriers, observe the following warning: Warning explosion hazard. Do not disconnect equip-

ment unless power has been switched off or the area is known to be nonhazardous.

7. Wiring between the sensor and safety barriers should comply with all relevant national standards and/or those standards set forth by

the authority having jurisdiction at the installation site. These may include Article 504 of the NEC, ANSI/ISA RP--12.6 (United States),

or CSA C22.2 (Canada).

8. Intrinsically Safe wiring must be separated from nonintrinsically safe wiring by at least 50mm (2in). The use of tiedowns, grounded

metal partitions, or approved insulating partitions are acceptable.

9. Intrinsically safe wiring shall be identified as such with labels placed no more than 7.62m (25ft) apart. The color light blue is interna-

tionally recognized as identifying intrinsically safe wiring.

10. The use of a gas-tight seal is required at the point where the wiring transitions the hazardous and nonhazardous location.
11. Intrinsically safe associated apparatus, cable shields, enclosures, and raceways (metal) shall be grounded in accordance with the

requirements of Section 250 of the NEC.

12. Nonhazardous location equipment must not contain a source voltage of greater than 250V unless sufficient means have been

employed to prevent the shorting of a source voltage greater than 250V onto the nonintrinsically safe terminals of the associated

apparatus.

13. Nonhazardous location equipment must not contain a source voltage of greater than 250V.
14. As all wiring contains stored energy (capacitance and inductance), all conductors must be considered when determining the length of

intrinsically safe circuits. When available the actual values should be used. If not available, values of 60pF/foot for capacitance per

wire pair and 0.2uH/foot for inductance are accepted and may be used.

15. Maximum operating ambient temperature range: --34_C to +70_C Type 4X.
16. Changes to this document are not permitted without prior approval by the testing agency.
17. WARNING: Potential electrostatic discharge hazard. Do not rub with dry cloth.

Rockwell Automation/Allen-Bradley
Control Drawing #75002--200--01(Ver 03)