Follow these steps to install the units.
1. Remove the protective caps from the stab openings or open the manual
shutters if present (automatic shutters open as the units are inserted).
2. Place the unit on the unit support pan and slide it into the section until it
is flush with the front of the structure and the power stabs are connected to
the vertical bus.
ATTENTION: De-energize all units before installing or removing.
When installing or removing MCC units, when possible, de-energize, lockout, and 
tag-out all sources of power to the MCC. If the MCC units are installed or removed 
with power applied to the main power bus, follow established electrical safety 
work practices. Refer to the NFPA 70E Standard for Electrical Safety in the 
Workplace publication.
Review your company safety lockout and tag-out procedure.
If power sources are connected to the motor control center, use extreme caution 
when inserting units. All buses and the line sides of the inserted units are 
energized, and contact with these parts can cause injury or death.
All covers and doors must be in place before applying power to the MCC. If units are 
removed, they must be replaced with the appropriate items, such as units, doors, 
and unit support pans.
ATTENTION: Plug-in MCC units can be heavy or awkward to handle. Use an 
assistant or a platform lift device if necessary to help you handle the unit.
ATTENTION: For 0.5 space factor units, a style 3 unit-support pan with bushing
must be used below the unit for proper operation of the latch/interlock 
mechanism. If the unit support pan with bushing is not used, the unit could be 
removed under load, resulting in injury or death.
TIP
Reposition your hands as necessary to properly support the unit while you are 
installing the unit into the MCC.
TIP
For Feeder units, you need to tilt the top of the unit slightly to the rear to avoid 
interference with the top angle latch bracket. If you do not have enough 
clearance, you need to loosen the angle latch bracket screw (approximately 